2022-02-10 08:36:45 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21101200 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) IN THE SUPPORTING DOCUMENTS FOLDER THERE ARE 2 FILES |
| NAMED ENERGY CALCULATIONS, ONE IS NAMED ENERGY |
| CALCULATIONS ? V2 DATED 1/31/2022, THE OTHER IS NAMED |
| ENERGY CALCLATIONS DATED 10/26/2021. THE FILE DATED |
| 10/26/2021 IS IN FACT THE ENERGY CALCULATIONS. THE ONE |
| DATED 1/31/2022 IS LABELED WRONG AS IT IS THE |
| MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE |
| CORRECT THIS. |
| |
| 2) SHEET M101: THERE IS A NOTE THAT READS FINAL DUCT |
| ARRANGEMENTS RESERVED PENDING STRUCTURAL COORDINATION. |
| PLEASE PROVIDE THE FINAL DOCUMENTS AS WE SHOULD BE |
| REVIEWING THE FINAL CODE COMPLIANT DRAWINGS. IF THESE |
| ARE THE FINAL DRAWINGS THEN PLEASE REMOVE THE NOTE. FBC |
| 107.2.1 |
| |
| 3) PLEASE MAKE THE RETURN AIR PATH CLEAR IN ALL AREAS. |
| AHU-1-01 APPEARS TO HAVE THE RETURN TO THE RIGHT SIDE |
| OF THE CLOSET WITH THE LEFT SIDE OF THE UNIT BEING THE |
| SUPPLY SIDE. F12 IS LEAVING THE RIGHT SIDE OF THIS UNIT |
| BUT THE ARROWS INDICTING THE FLOW SHOWS IT IS SUPPLYING |
| AIR TO THE GUEST SUITE 1. F9 DUCT IS LEAVING FROM THE |
| LEFT SIDE OF THE UNIT THAT INDICATES A FLOW TO THE |
| GUEST SUITE 1 BUT THE ARROW AT THE DIFFUSER INDICATES |
| THE FLOW IS RETURNING BACK TO THE UNIT. FBC 107.2.1 |
| |
| 4) PLEASE SHOW THE CONDENSATE DRAIN PIPE SIZES FOR EACH |
| SECTION OF PIPE. IT APPEARS THAT ALL PIPE SIZES LEAVING |
| EACH UNIT IS 1 INCH BUT THE ONLY REFERENCE TO THE |
| DRAINAGE SYSTEM SIZE IS AT THE CONDENSATE GOOSENECK ON |
| THE EXTERIOR OF THE BUILDING WHICH IS 2 INCH PVC. FBC |
| RES M1411.3.2 |
| |
| 5) PLEASE SHOW THE CALCULATIONS FOR THE CONDENSATE PIPE |
| SIZING BASED ON FBC M TABLE 307.2.2 |
| |
| 6) PLEASE SHOW HOW THIS CONDENSATE DRAINAGE DESIGN WILL |
| BE CODE COMPLIANT WITH THE DRAIN LINE MAINTENANCE OF |
| FBC RES M1411.3.3 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |