2022-02-10 08:36:451ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21101200
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN THE SUPPORTING DOCUMENTS FOLDER THERE ARE 2 FILES
 NAMED ENERGY CALCULATIONS, ONE IS NAMED ENERGY
 CALCULATIONS ? V2 DATED 1/31/2022, THE OTHER IS NAMED
 ENERGY CALCLATIONS DATED 10/26/2021. THE FILE DATED
 10/26/2021 IS IN FACT THE ENERGY CALCULATIONS. THE ONE
 DATED 1/31/2022 IS LABELED WRONG AS IT IS THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE
 CORRECT THIS.
  
 2) SHEET M101: THERE IS A NOTE THAT READS FINAL DUCT
 ARRANGEMENTS RESERVED PENDING STRUCTURAL COORDINATION.
 PLEASE PROVIDE THE FINAL DOCUMENTS AS WE SHOULD BE
 REVIEWING THE FINAL CODE COMPLIANT DRAWINGS. IF THESE
 ARE THE FINAL DRAWINGS THEN PLEASE REMOVE THE NOTE. FBC
 107.2.1
  
 3) PLEASE MAKE THE RETURN AIR PATH CLEAR IN ALL AREAS.
 AHU-1-01 APPEARS TO HAVE THE RETURN TO THE RIGHT SIDE
 OF THE CLOSET WITH THE LEFT SIDE OF THE UNIT BEING THE
 SUPPLY SIDE. F12 IS LEAVING THE RIGHT SIDE OF THIS UNIT
 BUT THE ARROWS INDICTING THE FLOW SHOWS IT IS SUPPLYING
 AIR TO THE GUEST SUITE 1. F9 DUCT IS LEAVING FROM THE
 LEFT SIDE OF THE UNIT THAT INDICATES A FLOW TO THE
 GUEST SUITE 1 BUT THE ARROW AT THE DIFFUSER INDICATES
 THE FLOW IS RETURNING BACK TO THE UNIT. FBC 107.2.1
  
 4) PLEASE SHOW THE CONDENSATE DRAIN PIPE SIZES FOR EACH
 SECTION OF PIPE. IT APPEARS THAT ALL PIPE SIZES LEAVING
 EACH UNIT IS 1 INCH BUT THE ONLY REFERENCE TO THE
 DRAINAGE SYSTEM SIZE IS AT THE CONDENSATE GOOSENECK ON
 THE EXTERIOR OF THE BUILDING WHICH IS 2 INCH PVC. FBC
 RES M1411.3.2
  
 5) PLEASE SHOW THE CALCULATIONS FOR THE CONDENSATE PIPE
 SIZING BASED ON FBC M TABLE 307.2.2
  
 6) PLEASE SHOW HOW THIS CONDENSATE DRAINAGE DESIGN WILL
 BE CODE COMPLIANT WITH THE DRAIN LINE MAINTENANCE OF
 FBC RES M1411.3.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  