Plan Review Notes
Plan Review Notes For Permit 21101200
Permit Number 21101200
Review Stop M
Sequence Number 1
Notes
Date Text
2021-11-09 09:42:301ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21101200
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS HAVE
 ONLY 8 SHEETS OUT OF 61. PLEASE SUBMIT THE ENTIRE
 DOCUMENT FOR REVIEW. FBC 107.2.1
  
 2) PLEASE SHOW ON THE DRAWING THAT THE COMBUSTION AIR
 GRILL IS A MINIMUM OF 10 FT AWAY FROM THE GENERATOR
 EXHAUST. FBC 107.2.1
  
 3) PLEASE SHOW THE EXHAUST FAN FOR THE SHOWER AREA FOR
 THE SUITE 3 BATHROOM. FBC RES M1507.4
  
 4) PLEASE SHOW THE SIZE AND MATERIAL USED FOR THE
 CONDENSATE PIPING. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  