Plan Review Notes
Plan Review Notes For Permit 21101119
Permit Number 21101119
Review Stop E
Sequence Number 1
Notes
Date Text
2021-11-02 09:28:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PERMIT APPLICATION STATES THIS IS FOR A PANEL
 CHANGE, THE DRAWINGS SUGGEST MUCH MORE WIRING TO BE
 DONE
 2) VALUATION IS AT $3,800
 3) I ASSUME WHAT IS ON THE DRAWING IS NEW, BUT CAN?T BE
 SURE
 4) I ASSUME POU WATER HEATER IS A TANKLESS STYLE WATER
 HEATER, IF SO IT IS ONLY LISTED ON THE ATTACHED LOAD
 CALCULATION AS 4500WATTS. IF THIS THE ONLY WATER HEATER
 AND IS A TANKLESS IT WOULD BE WAY TOO SMALL
 5) NOT ENOUGH DETAIL SHOWING WHAT IS NEW AND WHAT IS
 EXISTING. IS THERE A NEW A/C, ETC. ?
 6) THEY SHOULD SUBMIT A MORE DETAILED DRAWING AND WORK
 SCOPE THAT CAN BE MORE EASILY UNDERSTOOD
  
  