2022-04-08 13:58:49SYSTEM MUST MEET THE REQUIREMENTS OF NFPA 101 CH. 7
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES.
 DOOR ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE
 PERMITTED TO
 BE ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED,
 LISTED HARDWARE,
 PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
  
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO
 THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS
 READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND
 IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY
 DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR
 ASSEMBLY
 IN THE DIRECTION OF EGRESS.
 (5)*LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  