Notes |
Date |
Text |
2022-04-08 13:58:49 | SYSTEM MUST MEET THE REQUIREMENTS OF NFPA 101 CH. 7 | | | | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR | | ASSEMBLIES. | | DOOR ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE | | PERMITTED TO | | BE ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, | | LISTED HARDWARE, | | PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET: | | | | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS | | AFFIXED TO | | THE DOOR LEAF. | | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION | | THAT IS | | READILY OPERATED IN THE DIRECTION OF EGRESS. | | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE | | HAND | | IN THE DIRECTION OF EGRESS. | | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER | | SUPPLY | | DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR | | ASSEMBLY | | IN THE DIRECTION OF EGRESS. | | (5)*LOSS OF POWER TO THE LISTED RELEASING HARDWARE | | AUTOMATICALLY | | UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. | | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN | | ACCORDANCE WITH | | ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | INSPECTIONS AND APPROVAL. | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] | | |
|