2021-10-28 16:31:47ROOFING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1.PROVIDE ENHANCED FASTENER CALCULATIONS PER NOTE #7 ON
 NOA 21-0303.20, PREPARED BY A QUALIFIED DESIGN
 PROFESSIONAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
 2. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER
 BARRIER PER FBC R905.1.1.
 UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL
 CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE
 APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION
 R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  