2021-11-19 21:44:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. MINIMUM WIRE SIZE FOR 7.5KVA SINGLE PHASE STEP DOWN |
| TRANSFORMER IS #12 CU. NEC 110.14C1A2 |
| |
| 2. PRIMARY OCP FOR 7.5 KVA TRANSFORMER SHOULD BE |
| 20AMPS. NEC 215.3A, 450.3B1. 240.4 |
| |
| 3. SECONDARY OCP FOR 7.5KVA TRANSFORMER SHOULD BE |
| 40AMPS MAX. NEC 215.3A 408.36 |
| |
| 4. EGC SHOWN FROM METER CAN TO SERVICE DISCONNECTING |
| MEANS. THIS IS A PARALLEL PATH BACK TO GROUNDED |
| CONDUCTOR. EGC ORIGINATES AT 1ST MEANS OF DISCONNECT ON |
| LOAD SIDE. PLEASE REMOVE. NEC 250.24 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-805-6744 |
| |