2021-11-19 21:44:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MINIMUM WIRE SIZE FOR 7.5KVA SINGLE PHASE STEP DOWN
 TRANSFORMER IS #12 CU. NEC 110.14C1A2
  
 2. PRIMARY OCP FOR 7.5 KVA TRANSFORMER SHOULD BE
 20AMPS. NEC 215.3A, 450.3B1. 240.4
  
 3. SECONDARY OCP FOR 7.5KVA TRANSFORMER SHOULD BE
 40AMPS MAX. NEC 215.3A 408.36
  
 4. EGC SHOWN FROM METER CAN TO SERVICE DISCONNECTING
 MEANS. THIS IS A PARALLEL PATH BACK TO GROUNDED
 CONDUCTOR. EGC ORIGINATES AT 1ST MEANS OF DISCONNECT ON
 LOAD SIDE. PLEASE REMOVE. NEC 250.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved