Plan Review Notes
Plan Review Notes For Permit 21101008
Permit Number 21101008
Review Stop M
Sequence Number 2
Notes
Date Text
2021-12-17 10:01:54PLEASE ADDRESS THE 1ST CYCLE REVIEW COMMENTS BELOW:
  
 2) AS THIS IS AN APARTMENT BUILDING PLEASE SHOW THE
 REQUIRED FIRE SEPARATION BETWEEN TENANTS. HOW IS THE
 DUCT WORK FOR THE APARTMENTS ON THE FIRST FLOOR RUN TO
 PREVENT THE NEED FOR RADIATION DAMPERS IN THE
 CEILING/FLOOR ASSEMBLY? FBC M 607
  
 3) PLEASE SHOW THE DUCTWORK FOR THE BATH EXHAUST FANS
 AND THE TERMINATION LOCATIONS. FBC M 501; FBCM 607
  
 4) PLEASE PROVIDE THE DRYER DUCT AND THE TERMINATION
 LOCATIONS. HOW IS THIS DRYER DUCT PENETRATING THE FLOOR
 OF THE UNIT ABOVE AND HOW ARE YOU PROTECTING THIS
 PENETRATION? FBC M 504; FBC M 607
  
 5) IS THERE GOING TO BE A HOOD OVER THE RANGES? IF SO,
 ARE THEY DUCTED TO THE OUTDOORS? FBC 107.2.1
  
 6) PLEASE SHOW THE CONDENSATE PIPING FOR EACH
 MECHANICAL UNIT AND THE TERMINATION LOCATION. FBC M 307
  
 7) THE TITLE BLOCK FOR THIS PROJECT IS CALLING THIS A
 ?PROPOSED RESIDENCE? PLEASE CLARIFY AS THIS IS AN
 APARTMENT BUILDING. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  