Plan Review Notes For Permit 21100968 |
Permit Number |
21100968 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-27 08:00:06 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENTS | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | APPROVAL (18-0919.07) REQUIRES ADDITIONAL SIGNED AND | | SEALED ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER | | FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER | | PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL | | (-52.5) - SEE GENERAL LIMITATION NUMBER 7 ON THE | | PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR | | DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED | | TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND | | DESIGN DATA USED PER 2020 FBC AND ASCE 7-16 - WIND | | SPEED - EXPOSURE - RISK CATEGORY - ETC. | | |
|