Notes
Date Text
2021-11-04 11:02:4310/22/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PERMIT ISSUED REQUIRES A GAS PERMIT FOR THE
 TANK-LESS, AND THERE IS NO PERMIT ON FILE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. THE VALUE FOR THE TANKLESS NEEDS TO BE ADDED TO THE
 PERMIT PER THE WPB AMENDMENTS TO THE FBC 109.3 BUILDING
 PERMITS VALUATIONS.
  
 3. WOULD YOU PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 4. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 5. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 6. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL
 BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING
 EHD NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 8. IF APPLICABLE, LIST THE BTU LOAD OF EACH APPLIANCE
 AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020
 FBC FG SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1)
 THROUGH 402.4 (37) OR 2020 FBC RES. SEC. G2413.
  
 9. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE 2020 FBC RES. SEC. G2413.4.1.
  
 10. WOULD YOU PLEASE INDICATE THE SYSTEM'S DELIVERY
 PRESSURE (PSI) ON THE PLAN PER THE 2020 FBC FG SEC.
 402.2 OR 2020 FBC RES. SEC. G2413.2.
  
 11. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT
 OF REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC
 RES. SEC G2421.2.
  
 12. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE
 ON GAS ISOMERIC PER THE 2020 FBC SEC. G2420.5.
  
 13. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS.
  
 14. WOULD YOU PLEASE SHOW AND LABEL DRIP LEG ON
 EQUIPMENT INSTALLED, EXCEPT FOR APPLIANCES, RANGE,
 DRYERS & OD GRILLS PER THE 2020 FBC RES. SEC. G2419.2.
  
 15. THIS TANK-LESS UNIT CALL FOR A 10.5 INCHES WATER
 COLUMN, AND THE SERVICE METER DISCHARGES IS A 12 INCHES
 WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER
 THE MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 16. IF UNITS REQUIRE CONDENSATE, THEY WILL NEED TO BE
 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC R318.5.
  
 17. WOULD YOU PLEASE INDICATE ON THE PLAN IF THE
 TANK-LESS WATER HEATER IS THE ONLY GAS APPLIANCE IN
 THIS SYSTEM? IF NOT, SUBMIT A COMPLETE GAS RISER
 SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED
 LENGTH TO THE FURTHEST GAS OUTLET, THE BTU LOAD OF EACH
 APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE OF GAS, AND
 THE TOTAL BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS
 ALSO APPLY TO A NEW GAS SYSTEM PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 18. WOULD YOU PLEASE SHOW ON THE HOUSE PLAN SHOW THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 19. A SUB ELECTRICAL PERMIT IS REQUIRED FOR IGNITION
 SOURCE PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 20. WOULD YOU PLEASE INDICATE ON THE PLAN IF THE
 TANK-LESS WATER HEATER IS REPLACING AN EXISTING
 TANK-LESS WATER HEATER, IS IT REPLACING A STORAGE
 TANK-TYPE WATER HEATER, OR IS IT BEING ADDED TO THE
 EXISTING HOT WATER SYSTEM? INDICATE THE APPLICATION IN
 THE DESCRIPTION OF WORK PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR