2022-02-04 10:46:25 | 3RD REVIEW FBC-2020 PLUMBING |
| PERMIT- 21100660 |
| 2/4/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| FAIR HOUSING DESIGN ACT MANUAL |
| |
| PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST AND |
| 2ND REVIEW STILL EXIST. I AM REQUESTING THAT THE |
| CONTRACTOR/DESIGNER FOR THE PROJECT CONTACT ME TO GO |
| OVER THE PLANS EITHER BY TELPHONE OR ZOOM CALL. PLEASE |
| NOTE THE PLUMBING PLANS SHALL BE SIGNED BY A FL. |
| LICENSED ENGINEER OR PLUMBING CONTRACTOR. PLUMBING |
| CONTRACTOR PLANS SHALL BEAR THE PRINTED NAME, LICENSE |
| NUMBER AND SIGNATURE OF THE CONTRACTOR- SEC. 107.2.1 |
| WPB. |
| |
| 1) SHEET P1: THE SANITARY ISOMETRIC DRAWING DOES NOT |
| APPEAR TO REFLECT THE ACTUAL BUILDING DRAIN LAYOUT AS |
| SHOWN ON THE FLOOR PLAN. A) BASED ON THE FLOOR PLAN THE |
| KITCHEN SINK DRAIN SHALL CONNECT DOWNSTREAM OF THE |
| WASHING MACHINE DRAIN CONNECTION AND BE INDIVIDUALLY |
| VENTED- SECS. 910 & 911 FBC P. B) THE HAIR SINK DRAINS |
| SHALL CONNECT DOWNSTREAM OF THE WC AND LAV AND SHALL BE |
| INDIVIDUALLY VENTED IN ACCORDANCE WITH SECS. 910 & |
| 912.1 FBC P. |
| |
| 2) P1: THE NOTES INDICATE A STACKABLE WD, HOWEVER THE |
| PLANS SHOW THE UNITS SIDE BY SIDE. PLEASE CORRECT- SEC. |
| 107.2.1 WPB. |
| |
| 3) P2: THE 1ST REVIEW COMMENT #2 STILL PARTIALLY |
| EXISTS. A) PLEASE SHOW LAVATORY KNEE AND TOE |
| CLEARANCES- PAGES 7.47- 7.52 FHDA. B) PLEASE SHOW THE |
| DEPTH MEASUREMENT OF THE NEW SHOWER TO BE NO LESS THAN |
| 36-INCHES PER PAGE 7.58 FHDA. |
| |
| 4) P2: THE 1ST REVIEW COMMENT #3 REQUESTING GRAB BAR |
| REINFORCEMENT LOCATIONS STILL EXISTS. PLEASE PROVIDE |
| ELEVATION DRAWINGS IN ACCORDANCE WITH- |
| PAGES 6.3- 6.8- WATER CLOSETS. |
| PAGES 6.12- 6.13- SHOWERS |
| PAGES 6.14- 6.16 REINFORCEMENT METHODS |
| FOR ADDITIONAL DRAWINGS PLEASE SEE FIGURES 3 & 5 OF THE |
| FAIR HOUSING ACCESSIBILITY GUIDELINES CONTAINED IN THE |
| FBC ACC. |
| |
| 5) P2: THE HEIGHT MEASUREMENT FOR THE SHOWER SEAT IS |
| NOT LEGIBLE. PLEASE REFER TO PAGE 6.13 FHDA. THE HEIGHT |
| SHALL BE 17-19 INCHES FROM THE FINISHED SHOWER FLOOR. |
| |
| 6) THE REQUESTED WATER DISTRIBUTION RISER WAS NOT |
| PROVIDED. PLEASE PROVIDE THE DRAWING WHICH SHALL |
| INCLUDE THE LOCATION OF THE WATER HEATER AND HOT WATER |
| PIPING PLAN- SEC. 607.1 FBC P. |
| |
| 7) P2: PLEASE SHOW THE CENTERLINE OF THE WATER CLOSET |
| DRAIN WILL BE 18 INCHES MEASURED FROM THE ADJACENT |
| FINISHED WALL- PAGE 7.43 FHDA. |
| |
| 8) P3: SHOW THE SHOWER PAN LINER WILL BE PITCHED ONE |
| FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL (1/4 INCH |
| PER FT. OR 2% SLOPE)- SEC. 417.5.2 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |