Plan Review Notes
Plan Review Notes For Permit 21100660
Permit Number 21100660
Review Stop M
Sequence Number 3
Notes
Date Text
2022-02-10 13:57:43THE DRAWING HAS CHANGED, PLEASE PROVIDE A CODE
 COMPLIANT MECHANICAL DRAWING SHOWING THIS BEAUTY SALON
 AND THE MECHANICAL SYSTEMS ASSOCIATED WITH A BEAUTY
 SALON ALONG WITH ADDRESSING THE COMMENTS FROM THE FIRST
 CYCLE MECHANICAL PLAN REVIEW LISTED BELOW.
  
 PLEASE RESPOND TO FIRST CYCLE MECHANICAL REVIEW
 COMMENTS BELOW:
  
 PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE
 MECHANICAL WORK COVERED UNDER THIS PROJECT. I.E. MOVING
 OF SUPPLY OR RETURN REGISTERS, THE DRYER EXHAUST DUCT
 AND TERMINATION LOCATION, THE BATHROOM EXHAUST FANS.
 AND THE TERMINATION LOCATIONS. IS THERE GOING TO BE A
 HOOD ABOVE THE RANGE? IF SO WILL IT BE DUCTED TO THE
 EXTERIOR? WHAT ARE THE EXHAUST CFM'S? DOES IT REQUIRE
 MAKE UP AIR? FBC 107.2.1
  
  