2022-01-10 09:55:322ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21100660
 1/10/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE SANITARY ISOMETRIC DRAWING DOES NOT
 APPEAR TO REFLECT THE ACTUAL BUILDING DRAIN LAYOUT AS
 SHOWN ON THE FLOOR PLAN. A) BASED ON THE FLOOR PLAN THE
 KITCHEN SINK DRAIN SHALL CONNECT DOWNSTREAM OF THE
 WASHING MACHINE DRAIN CONNECTION AND BE INDIVIDUALLY
 VENTED- SECS. 910 & 911 FBC P. B) THE HAIR SINK DRAINS
 SHALL CONNECT DOWNSTREAM OF THE WC AND LAV AND SHALL BE
 INDIVIDUALLY VENTED IN ACCORDANCE WITH SEC. 912.1 WET
 VENTING FBC P.
  
 2) P1: THE NOTES INDICATE A STACKABLE WD, HOWEVER THE
 PLANS SHOW THE UNITS SIDE BY SIDE. PLEASE CORRECT- SEC.
 107.2.1 WPB.
  
 3) P2: THE 1ST REVIEW COMMENT #2 STILL PARTIALLY
 EXISTS. A) PLEASE SHOW LAVATORY KNEE AND TOE
 CLEARANCES- PAGES 7.47- 7.52 FHDA. B) PLEASE SHOW THE
 DEPTH MEASUREMENT OF THE NEW SHOWER TO BE NO LESS THAN
 36-INCHES PER PAGE 7.58 FHDA.
  
 4) P2: THE 1ST REVIEW COMMENT #3 REQUESTING GRAB BAR
 REINFORCEMENT LOCATIONS STILL EXISTS. PLEASE PROVIDE
 ELEVATION DRAWINGS IN ACCORDANCE WITH-
 PAGES 6.3- 6.8- WATER CLOSETS.
 PAGES 6.12- 6.13- SHOWERS
 PAGES 6.14- 6.16 REINFORCEMENT METHODS
 FOR ADDITIONAL DRAWINGS PLEASE SEE FIGURES 3 & 5 OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES CONTAINED IN THE
 FBC ACC.
  
 5) P2: THE HEIGHT MEASUREMENT FOR THE SHOWER SEAT IS
 NOT LEGIBLE. PLEASE REFER TO PAGE 6.13 FHDA. THE HEIGHT
 SHALL BE 17-19 INCHES FROM THE FINISHED SHOWER FLOOR.
  
 6) THE REQUESTED WATER DISTRIBUTION RISER WAS NOT
 PROVIDED. PLEASE PROVIDE THE DRAWING WHICH SHALL
 INCLUDE THE LOCATION OF THE WATER HEATER AND HOT WATER
 PIPING PLAN- SEC. 607.1 FBC P.
  
 7) P2: PLEASE SHOW THE CENTERLINE OF THE WATER CLOSET
 DRAIN WILL BE 18 INCHES MEASURED FROM THE ADJACENT
 FINISHED WALL- PAGE 7.43 FHDA.
  
 8) P3: SHOW THE SHOWER PAN LINER WILL BE PITCHED ONE
 FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL (1/4 INCH
 PER FT. OR 2% SLOPE)- SEC. 417.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  