2021-11-15 15:13:14 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21100660 |
| 11/15/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| FAIR HOUSING DESIGN ACT MANUAL |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A-1: PROVIDE DESIGN CRITERIA FOR THE PROJECT |
| INCLUDING A LIST OF CURRENT CODES AND STANDARDS- |
| SECTION 107.2.1 WPB. |
| |
| 2) A-1 & P-1: FAIR HOUSING ACT COMPLIANCE: TWO CITY |
| PLAZA IS A MULTI-STORY CONDOMINIUM BUILDING THAT WERE |
| DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE FAIR |
| HOUSING ACT DESIGN GUIDELINES. REFER TO PAGE 7 OF THE |
| MANUAL WHICH REQUIRES THE GROUND FLOOR LEVEL OF UNIT |
| 101 TO IN COMPLIANCE WITH THE GUIDELINES. |
| A) THE DESIGN PROFESSIONAL OF RECORD SHALL INDICATE ON |
| THE PLANS WHICH OF THE TWO BATHROOM TYPES IS THE BASIS |
| OF DESIGN- SPECIFICATION TYPE A OR B ON THE PLANS. |
| PLEASE REFER TO PAGES 7.34- 7.39 OF THE DESIGN MANUAL |
| FOR EXPLANATORY INFORMATION ON SPECIFICATION A & B AND |
| SHOW COMPLIANCE. |
| 2) REFER TO CHAPTER 7 (REQUIREMENT 7 USABLE KITCHENS & |
| USABLE BATHROOMS) AND PROVIDE ENLARGED, DIMENSIONED |
| KITCHEN AND BATHROOM DRAWINGS AND DETAILS. THE PLANS |
| SHALL BE IN COMPLIANCE WITH THE SECTIONS LISTED BELOW- |
| PAGES 7.1- 7.6 CLEAR FLOOR SPACES FOR SINKS AND |
| APPLIANCES |
| PAGES 7.7- 7.11 CLEARANCES BETWEEN KITCHEN COUNTERS AND |
| ALL OPPOSING ELEMENTS. |
| PAGES 7.12- 7.16 REMOVABLE SINK AND APPLIANCE CABINET |
| DOORS INCLUDING KNEE SPACES. |
| PAGES 7.40-7.46 WATER CLOSET CLEAR FLOOR SPACES. |
| PAGES 7.47- 7.52: LAVATORY AND VANITY CLEAR FLOOR AND |
| KNEE AND TOE CLEARANCES. |
| PAGES 7.56- 7.59: SHOWER CLEAR FLOOR SPACE AND CONTROL |
| LOCATIONS INCLUDING SHOWER DIMENSIONS. |
| |
| 3) REFER TO CHAPTER 6 (REINFORCED WALLS FOR GRAB BARS). |
| BASED ON CHAPTER 7 COMPLIANCES LISTED ABOVE, PLEASE |
| PROVIDE DRAWINGS AND DETAILS SHOWING GRAB BAR |
| REINFORCEMENT LOCATIONS AND INSTALLATION DETAILS. |
| PAGES 6.3- 6.8- WATER CLOSETS. |
| PAGES 6.12- 6.13- SHOWERS |
| PAGES 6.14- 6.16 REINFORCEMENT METHODS |
| |
| 4) P-1: THE ISOMETRIC DRAWING DOES NOT SHOW THE |
| REQUIRED VENTS FOR THE PLUMBING FIXTURES- SECTION |
| 901.2.1 FBC P. |
| |
| 5) P-1: THE 2-INCH VERTICAL DRAIN STACK AND HORIZONTAL |
| BRANCH ARE UNDERSIZED- MINIMUM 3-INCH DRAINS ARE |
| REQUIRED- SECTION 406.2 FBC P. |
| |
| 6) P-1: PLEASE OUTLINE THE NEW DRAIN LOCATIONS ON THE |
| FLOOR PLAN AND PROVIDE A SLAB REPAIR DETAIL- SECTION |
| 107.2.1 WPB. |
| |
| 7) P-1: PROVIDE A WATER DISTRIBUTION RISER DRAWING- |
| SECTION 107.3.5.1.3 WPB. PROVIDE SYMBOLS ON THE DRAWING |
| TO INDICATE LOCATIONS OF REQUIRED WATER HAMMER |
| ARRESTORS AND BACKFLOW PREVENTERS- SECTION 604.9 & |
| 608.3 FBC P. |
| |
| 8) P-1 & P-2: PROVIDE A PLUMBING FIXTURE SCHEDULE |
| LISTING THE MAKES AND MODELS OF THE WATER CLOSETS, |
| LAVATORIES, SHOWER VALVES AND FAUCETS, KITCHEN SINK, |
| DISHWASHING MACHINE, WASHING MACHINE- SECTIONS 405- 425 |
| FBC P. |
| |
| 9) P-1 & P-2: INDICATE THE TYPE OF FINISH MATERIALS FOR |
| THE FLOORS AND WALLS OF THE SHOWERS- 421.5.1 AND |
| PROVIDE A SHOWER PAN DETAIL- 421.5.2 FBC P. |
| |
| 10) P-1: INDICATE THE TYPE OF 2X4 WOOD BACKING TO BE |
| INSTALLED FOR THE GRAB BAR REINFORCEMENTS AND PROVIDE |
| INSTALLATION DETAILS- SECTIONS 603.1 AND 1607.8.2 FBC |
| B. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |