Plan Review Notes For Permit 21100652 |
Permit Number |
21100652 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2022-10-11 07:32:07 | 3RD PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | ---NOT ADDRESSSED---THE ENGINEER THAT DREW THE DRAWINGS | | MUST DIGITALLY SIGN WITH 3RD PARTY CERTIFICATION ALL OF | | THE DIGITALLY SUBMITTED DRAWINGS. F.S. 471,481. | | | | 1. ---NOT ADDRESSSED---MP-8/SANITARY RISER: PROVIDE | | FULL OPEN VALVE DOWNSTREAM OF CHECK VALVE IN SUMP PUMP | | DISCHARGE PER FBC PL 712.2. BOTH VALVES SHALL BE | | ACCESSIBLE. | | | | | | 4. ---NOT ADDRESSSED---MP-8: PROVIDE AN INDIVIDUAL VENT | | FOR P-4 SERVICE SINK. SHOW COMPLIANCE WITH FBC PL 909.1 | | AND 1002.3(5) | | | | | | 5. ---NOT ADDRESSSED--- PROVIDE CALCULATIONS FOR SIZING | | THE GRAVITY ROOF DRAIN COMPLYING WITH FBC PL TABLES | | 1106.2 AND 1106.3. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|