2022-08-16 15:37:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21100652 85 SOUTHERN BLVD
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 MOST COMMENTS FROM THE 1ST REVIEW COPIED BELOW WERE NOT
 ADDRESSED. NO CORRECTED PLANS HAVE BEEN PROVIDED FOR
 REVIEW.
 NEW COMMENT. IT APPEARS THAT PERMIT 21091249 AND THIS
 PERMIT 21100652 ARE FOR THE SAME PROJECT, ONE FOR
 MECHANICAL AND ONE FOR PLUMBING. THE SAME PLUMBING
 SCOPE HAS BEEN REVIEWED BY TWO (2) DIFFERENT PLANS
 EXAMINERS
  
 1.GENERAL NOTE: DEFERRED SUBMITTALS FBC 107.3.4.1
 REGARDING THE SUMP PUMP, POINT OF USE WATER HEATERS,
 ETC., DEFERRED SUBMITTALS IN THE FORM OF MANUFACTURERS
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS MAY BE
 SUBMITTED IN ACCORDANCE WITH WPB FBC 107.3.4.1 DEFERRED
 SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THEY SHALL
 BE SUBMITTED TO, APPROVED BY THE BUILDING OFFICIAL AND
 ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN
 RISK.
 BY PROVIDING THE NOTE ABOVE ON THE CONSTRUCTION
 DOCUMENTS TO BE REVIEWED AND LISTING THE ITEMS TO BE
 DEFERRED, YOU MAY PROCEED IN THIS MANNER.
 ENGINEER DID NOT ADDRESS. SOME ITEMS WERE SUBMITTED IN
 SECOND REVIEW, SOME WERE NOT.
  
 2.SECOND REQUEST:A REVIEW OF MINIMUM PLUMBING FIXTURE
 REQUIREMENTS AS REQUIRED BY FBC ACC IS PART OF THE
 PLUMBING REVIEW PROCESS BUT IS TYPICALLY ADDRESSED ON
 THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING THESE
 REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED PRIOR TO
 A PLUMBING REVIEW APPROVAL.
 THE RESTROOM DOES NOT APPEAR TO COMPLY WITH FBC ACC
 CHAPTERS 2, 3 AND 6. PER WPB FBC 107.2.1, CLARIFY.
 PLEASE REVIEW FBC ACC 203.9, 213.1. PROVIDE ELEVATIONS
 AND PLAN VIEW SHOWING COMPLIANCE WITH FBC ACC AS
 FOLLOWS AND IS APPLICABLE.
 A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E) FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
 I) PER FBC ACC 604.8.1.2 AND 604.8.1.7, THE DOOR TO THE
 ACCESSIBLE TOILET RM/COMPARTMENT SHALL BE LOCATED IN
 THE FRONT PARTITION OR IN THE SIDE WALL OR PARTITION
 FARTHEST FROM THE WATER CLOSET, DIAGONAL TO THE WATER
 CLOSET.
 J)LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 K) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606
 PER FBC ACC 212.3. DOES NOT APPLY TO A SERVICE SINK.
 L) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 M) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 N) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 O) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 OR
 304.3.2.
 ENGINEER'S RESPONSE: RESTROOMS DO NOT NEED TO BE ADA
 COMPLIANT. WILL REVISE NOTES ON PLUMBING FIXTURE
 SCHEDULE.
 NOTES HAVE NOT BEEN REVISED, HOWEVER, ADA COMPLIANT
 FIXTURES MAY BE PROVIDED.
  
 3.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 OCCUPANCY TYPE AND OCCUPANCY LOAD FOR STRUCTURE.
 PROVIDE FIXTURE SCHEDULE LISTING REQUIRED PLUMBING
 FIXTURES AND QUANTITIES REQUIRED BY FBC PL TABLE 403.1
 TO ACCOMMODATE THE STATED OCCUPANCY AND OCCUPANCY LOAD.
 ENGINEER'S RESPONSE: CONCUR. THIS STRUCTURE WILL HAVE 1
 STAFF MEMBER. WILL PROVIDE FIXTURE SCHEDULE LISTING
 REQUIRED PLUMBING FIXTURES AND QUANTITIES.
 OCCUPANCY TYPE AND LOAD HAVE NOT BEEN PROVIDED
  
 4. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE AN
 OVERALL FLOOR PLAN FOR EACH LEVEL SHOWING RESPECTIVE
 LOCATIONS OF PIER 6 AND PIER 7 AS WELL AS COMPREHENSIVE
 ELEVATION VIEW(S) IDENTIFYING THE LEVELS.
  
 5. SECOND REQUEST: MP-1: PER WPB FBC 107.2.1, SPECIFY A
 CARRIER SYSTEM FOR P-1 WATER CLOSET; PROVIDE
 MANUFACTURERS SPECIFICATION/INSTALLATION MANUAL FOR
 CARRIER SYSTEM FOR P-1 WATER CLOSET OR LIST AS A
 DEFERRED SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.1;
 SEE COMMENT #1.
  
 7. SECOND REQUEST: MP-1: FIXTURE SCHEDULE P-4 SERVICE
 SINK; PER WPB FBC 107.2.1, PROVIDE SUMP PUMP AND BASIN
 DETAIL SHOWING PIPING AND VALVE ARRANGEMENT SHOWING
 COMPLIANCE WITH FBC PL SECTION 712. PER FBC PL 712.2, A
 CHECK VALVE AND A FULL OPEN VALVE SHALL BE LOCATED IN
 THE DISCHARGE LINE FROM THE SUMP AND SHALL BE
 ACCESSIBLE.
  
 8. SECOND REQUEST: PROVIDE MANUFACTURERS
 SPECIFICATION/INSTALLATION MANUAL FOR SUMP PUMP OR LIST
 AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH FBC
 107.3.4.1; SEE COMMENT #1.
  
 9. SECOND REQUEST: MP-1: FIXTURE SCHEDULE P-4 SERVICE
 SINK; A VACUUM BREAKER IS REQUIRED ON THE FAUCET HOSE
 THREADS PER FBC PL 608.1 AND 608.2. PER WPB FBC
 107.2.1, SPECIFY AND ADD TO P-4 DESCRIPTION.
  
 10. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 TANKLESS WATER HEATER INSTALLATION DETAIL SHOWING
 PIPING AND VALVE ARRANGEMENT.
  
 11. SECOND REQUEST: PROVIDE MANUFACTURE'RS
 SPECIFICATION/INSTALLATION MANUAL FOR THE WATER HEATERS
 OR LIST AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH FBC
 107.3.4.1; SEE COMMENT #1.
 NEW COMMENT: SEE MP-6/NOTE 9: CALLS FOR ELECTRIC
 TANKLESS WATER HEATER 4.1 KW/14.8 AMPS, COORDINATE
 VOLTAGE WITH ELECTRICAL INSTALLER. PER WPB FBC 107.2.1,
 PROVIDE MANUFACTURER AND MODEL FOR WATER HEATER;
 ADDITIONALLY, IT IS NOTED TO A PERMIT IS REQUIRED FOR
 ELECTRICAL WORK. THERE IS NO ELECTRICAL SCHEDULE. THERE
 ARE NO ELECTRICAL DRAWINGS.
  
 12. SECOND REQUEST: MP-1: FIXTURE SCHEDULE P-2
 LAVATORY; FBC PL 419.5 REQUIRES COLD OR TEMPERED WATER
 SHALL BE DELIVERED FROM LAVATORIES AND GROUP WASH
 FIXTURES LOCATED IN PUBLIC TOILET FACILITIES PROVIDED
 FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 A) PER WPB FBC 107.2.1, PLEASE CLARIFY IF THERE IS TO
 BE PUBLIC ACCESS TO THE RESTROOM. COMPLIANT TEMPERED
 WATER DEVICES MAY BE PROVIDED IN ANY CASE BUT SHALL BE
 PROVIDED IF PUBLIC.
 B) PER WPB FBC 107.2.1, A SPECIFICATION WOULD BE
 REQUIRED.
 ENGINEER RESPONSE: CONCUR. WILL SPECIFY A THERMOSTATIC
 MIXING VALVE FOR TEMPERED WATER TO SERVICE SINK.
 LAVATORY SHALL ONLY BE PROVIDED WITH COLD WATER.
 NEW COMMENT: REVISED(?) PLANS DO NOT REFLECT COLD WATER
 ONLY TO P-2 AND STILL SHOW A WATER HEATER
  
 13. SECOND REQUEST: P-3 SINK AND P-4 SINK IN RISER
 BELOW P-2 LAVATORY, PER FBC PL 607.1, PROVIDE HOT
 WATER.
 ENGINEER RESPONSE: CONCUR. ELECTRIC WATER HEATER TO BE
 PROVIDED FOR SERVICE SINK ON MP-4.
 NEW COMMENT: REVISED(?) PLAN MP-8 DOES NOT REFLECT HOT
 WATER TO P-4 AND ELECTRIC WATER HEATER IS NOT SHOWN
  
 14. SECOND REQUEST: PROVIDE DETAIL FOR HB-1 WALL BOX
 AND SHUTOFF VALVE. WILL WALL BOX BE RECESSED INTO
 STRUCTURE?
  
 15. SECOND REQUEST: PROVIDE MANUFACTURERS
 SPECIFICATION/INSTALLATION MANUAL FOR THE WALL BOX OR
 LIST AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH FBC
 107.3.4.1; SEE COMMENT #1.
  
 16. SECOND REQUEST: MP-2: TAG NOTE 1: SUMP PIT AND PUMP
 BY OTHERS; PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SUMP
 PIT AND PUMP BY OTHERS SHOWING DIMENSIONS, PIPING AND
 VALVE ARRANGEMENT. COMPLY WITH FBC PL SECTION 712. PER
 FBC PL 712.2, A CHECK VALVE AND A FULL OPEN VALVE SHALL
 BE LOCATED IN THE DISCHARGE LINE FROM THE SUMP AND
 SHALL BE ACCESSIBLE. ADDITIONALLY, INDICATE THE PUMP
 DISCHARGE GPM SHOWING IT IS CAPABLE OF DISCHARGING THE
 COMBINED STORM WATER AND A/C CONDENSATE ENTERING THE
 PIT.
  
 17. SECOND REQUEST: MP-2: TAG NOTE 4: REFERS TO B1-424
 FOR ADDITIONAL INFORMATION. PER WPB FBC 107.2.1,
 PROVIDE REFERENCED DRAWING
  
 18. SECOND REQUEST: MP-4: NOTE 3: PER FBC PL 607.1,
 PROVIDE HOT WATER AND COLD WATER
  
 19. SECOND REQUEST: MP-4: NOTE 11: PER FBC PL 712.2, A
 CHECK VALVE AND A FULL OPEN VALVE SHALL BE LOCATED IN
 THE DISCHARGE LINE FROM THE SUMP AND SHALL BE
 ACCESSIBLE.
  
 20. SECOND REQUEST: MP-4: NOTE 10: PROVIDE DETAIL(S)
 FOR UTILITIES CONNECTION(S) OR DISPOSAL POINTS
  
 21. SECOND REQUEST: MP-4: PROVIDE NOTE FOR SUMP
 DISCHARGE CONNECTION TO BUILDING DRAIN "PER FBC PL
 712.3.5, PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL
 CONNECT TO A BUILDING SEWER, BUILDING DRAIN, SOIL
 STACK, WASTE STACK OR HORIZONTAL BRANCH DRAIN. WHERE
 THE DISCHARGE LINE CONNECTS INTO HORIZONTAL DRAINAGE
 PIPING, THE CONNECTION SHALL BE MADE THROUGH A WYE
 FITTING INTO THE TOP OF THE DRAINAGE PIPING AND SUCH
 WYE FITTING SHALL BE LOCATED NOT LESS THAN 10 PIPE
 DIAMETERS FROM THE BASE OF ANY SOIL STACK, WASTE STACK
 OR FIXTURE DRAIN."
  
 22. SECOND REQUEST: MP-5: NOTE 4; PER FBC PL 607.1,
 PROVIDE HOT WATER AND COLD WATER
 ENGINEER RESPONSE: CONCUR. ELECTRIC WATER HEATER TO BE
 PROVIDED FOR SERVICE SINK ON MP-4.
 NEW COMMENT: REVISED(?) PLAN MP-8 DOES NOT REFLECT HOT
 WATER TO P-4 AND ELECTRIC WATER HEATER IS NOT SHOWN
  
 23. SECOND REQUEST: MP-6: ADD TO NOTE 8, "VENT
 TERMINALS EXTENDING THROUGH THE WALL SHALL COMPLY WITH
 FBC PL 903.6"
  
 24. SECOND REQUEST: MP-8: STORM DRAIN PIPING AT FD;
 REPLACE P-TRAP WITH QUARTER BEND SWEEP. SEE FBC PL
 1002.3, 1101.6 AND 1103.1
  
 25. SECOND REQUEST: MP-8: PROVIDE AN INDIVIDUAL VENT
 FOR P-4 SERVICE SINK. SHOW COMPLIANCE WITH FBC PL 909.1
 AND 1002.3(5)
  
 26. SECOND REQUEST: MP-8: P-1 WATER CLOSET IS A WALL
 HUNG FIXTURE. PER WPB FBC 107.2.1, SHOW IN THE SANITARY
 RISER AS ABOVE FLOOR WALL CONNECTION.
  
 27. SECOND REQUEST: MP-8: STORM RISER; PER WPB FBC
 107.2.1, INCLUDE STORM DISCHARGE PIPING FROM SUMP.
  
 28. SECOND REQUEST: MP-8: PROVIDE NOTE FOR PUMP
 DISCHARGE CONNECTION TO BUILDING DRAIN "PER FBC PL
 712.3.5, PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL
 CONNECT TO A BUILDING SEWER, BUILDING DRAIN, SOIL
 STACK, WASTE STACK OR HORIZONTAL BRANCH DRAIN. WHERE
 THE DISCHARGE LINE CONNECTS INTO HORIZONTAL DRAINAGE
 PIPING, THE CONNECTION SHALL BE MADE THROUGH A WYE
 FITTING INTO THE TOP OF THE DRAINAGE PIPING AND SUCH
 WYE FITTING SHALL BE LOCATED NOT LESS THAN 10 PIPE
 DIAMETERS FROM THE BASE OF ANY SOIL STACK, WASTE STACK
 OR FIXTURE DRAIN."
  
 29. SECOND REQUEST: MP-8: PROVIDE HOT WATER ROUTING OR
 TANKLESS WATER HEATERS FOR P-3, P-4 IN WATER RISER
 BELOW P-2. IF PROVIDING ROUTING, SPECIFY TANKLESS
 HEATER THAT WILL ACCOMMODATE P-2, P-3 AND P-4.
  
 30. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE PIPE
 HANGER DETAIL WITH A NOTE STATING, "HORIZONTAL PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 31. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE PIPING
 MATERIAL SPEC FOR EACH SYSTEM TO INCLUDE PIPE, VALVES,
 FITTINGS AND JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6,
 7, 9 AND 11.
 A) ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
 B) DISCHARGE PIPING FROM SUMP PUMPS SHALL BE PRESSURE
 RATED IN ACCORDANCE WITH FBC PL SECTIONS 712.3.3.1 AND
 712.3.3.2, PROVIDE NOTE ON PLANS STATING THE SAME.
  
 32. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 SPECIFICATION FOR 1) HOT WATER PIPING INSULATION AND 2)
 CONDENSATE PIPING INSULATION
  
 33. SECOND REQUEST: MORE INFORMATION IS REQUIRED
 REGARDING THE STORM DRAIN. WHAT IS THE PURPOSE? IS THIS
 IN AN OPEN AREA SUBJECT TO RAINFALL?
 A) PER WPB FBC 107.2.1, CLARIFY. ADDITIONALLY, PROVIDE
 CALCULATIONS FOR SIZING THE GRAVITY DRAIN COMPLYING
 WITH FBC PL TABLES 1106.2 AND 1106.3.
 B) NOTE THE REQUIRED SLOPE FOR THE HORIZONTAL PIPING.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  