2022-01-04 17:10:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21100652 401 CLEMATIS ST
  
 1ST REVIEW
 PLUMBING COMMENTS:
 1.GENERAL NOTE: DEFERRED SUBMITTALS FBC 107.3.4.1
 REGARDING THE SUMP PUMP, POINT OF USE WATER HEATERS,
 ETC., DEFERRED SUBMITTALS IN THE FORM OF MANUFACTURERS
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS MAY BE
 SUBMITTED IN ACCORDANCE WITH WPB FBC 107.3.4.1 DEFERRED
 SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THEY SHALL
 BE SUBMITTED TO, APPROVED BY THE BUILDING OFFICIAL AND
 ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN
 RISK.
 BY PROVIDING THE NOTE ABOVE ON THE CONSTRUCTION
 DOCUMENTS TO BE REVIEWED AND LISTING THE ITEMS TO BE
 DEFERRED, YOU MAY PROCEED IN THIS MANNER.
  
 2.A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 THE RESTROOM DOES NOT APPEAR TO COMPLY WITH FBC ACC
 CHAPTERS 2, 3 AND 6. PER WPB FBC 107.2.1, CLARIFY.
 PLEASE REVIEW FBC ACC 203.9, 213.1. PROVIDE ELEVATIONS
 AND PLAN VIEW SHOWING COMPLIANCE WITH FBC ACC AS
 FOLLOWS AND IS APPLICABLE.
 ?A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 ?B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 ?C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ?D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ?E) FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 ?F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 ?G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 ?H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
 ?I) PER FBC ACC 604.8.1.2 AND 604.8.1.7, THE DOOR TO
 THE ACCESSIBLE TOILET RM/COMPARTMENT SHALL BE LOCATED
 IN THE FRONT PARTITION OR IN THE SIDE WALL OR PARTITION
 FARTHEST FROM THE WATER CLOSET, DIAGONAL TO THE WATER
 CLOSET.
 ?J)LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 ?K) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606
 PER FBC ACC 212.3. DOES NOT APPLY TO A SERVICE SINK.
 ?L) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ?M) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 ?N) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 ?O) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1
 OR 304.3.2.
  
 3.PER WPB FBC 107.2.1, PROVIDE OCCUPANCY TYPE AND
 OCCUPANCY LOAD FOR STRUCTURE. PROVIDE FIXTURE SCHEDULE
 LISTING REQUIRED PLUMBING FIXTURES AND QUANTITIES
 REQUIRED BY FBC PL TABLE 403.1 TO ACCOMMODATE THE
 STATED OCCUPANCY AND OCCUPANCY LOAD.
  
 4. PER WPB FBC 107.2.1, PROVIDE AN OVERALL FLOOR PLAN
 FOR EACH LEVEL SHOWING RESPECTIVE LOCATIONS OF PIER 6
 AND PIER 7 AS WELL AS COMPREHENSIVE ELEVATION VIEW(S)
 IDENTIFYING THE LEVELS.
  
 5. MP-1: PER WPB FBC 107.2.1, SPECIFY A CARRIER SYSTEM
 FOR P-1 WATER CLOSET; PROVIDE MANUFACTURERS
 SPECIFICATION/INSTALLATION MANUAL FOR CARRIER SYSTEM
 FOR P-1 WATER CLOSET OR LIST AS A DEFERRED SUBMITTAL IN
 ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1.
  
 6. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS
 SPECIFICATION/INSTALLATION MANUAL FOR CARRIER FOR P-2
 LAVATORY OR LIST AS A DEFERRED SUBMITTAL IN ACCORDANCE
 WITH FBC 107.3.4.1; SEE COMMENT #1.
  
 7. MP-1: FIXTURE SCHEDULE P-4 SERVICE SINK; PER WPB FBC
 107.2.1, PROVIDE SUMP PUMP AND BASIN DETAIL SHOWING
 PIPING AND VALVE ARRANGEMENT SHOWING COMPLIANCE WITH
 FBC PL SECTION 712. PER FBC PL 712.2, A CHECK VALVE AND
 A FULL OPEN VALVE SHALL BE LOCATED IN THE DISCHARGE
 LINE FROM THE SUMP AND SHALL BE ACCESSIBLE.
  
 8. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR SUMP PUMP OR LIST AS A DEFERRED SUBMITTAL IN
 ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1.
  
 9. MP-1: FIXTURE SCHEDULE P-4 SERVICE SINK; A VACUUM
 BREAKER IS REQUIRED ON THE FAUCET HOSE THREADS PER FBC
 PL 608.1 AND 608.2. PER WPB FBC 107.2.1, SPECIFY AND
 ADD TO P-4 DESCRIPTION.
  
 10. PER WPB FBC 107.2.1, PROVIDE TANKLESS WATER HEATER
 INSTALLATION DETAIL SHOWING PIPING AND VALVE
 ARRANGEMENT.
  
 11. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR THE WATER HEATERS OR LIST AS A DEFERRED
 SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT
 #1.
  
 12. MP-1: FIXTURE SCHEDULE P-2 LAVATORY; FBC PL 419.5
 REQUIRES COLD OR TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 ?A) PER WPB FBC 107.2.1, PLEASE CLARIFY IF THERE IS TO
 BE PUBLIC ACCESS TO THE RESTROOM. COMPLIANT TEMPERED
 WATER DEVICES MAY BE PROVIDED IN ANY CASE BUT SHALL BE
 PROVIDED IF PUBLIC.
 ?B) PER WPB FBC 107.2.1, A SPECIFICATION WOULD BE
 REQUIRED.
  
 13. P-3 SINK AND P-4 SINK IN RISER BELOW P-2 LAVATORY,
 PER FBC PL 607.1, PROVIDE HOT WATER.
  
 14. PROVIDE DETAIL FOR HB-1 WALL BOX AND SHUTOFF VALVE.
 WILL WALL BOX BE RECESSED INTO STRUCTURE?
  
 15. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR THE WALL BOX OR LIST AS A DEFERRED SUBMITTAL
 IN ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1.
  
 16. MP-2: TAG NOTE 1: SUMP PIT AND PUMP BY OTHERS; PER
 WPB FBC 107.2.1, PROVIDE DETAIL FOR SUMP PIT AND PUMP
 BY OTHERS SHOWING DIMENSIONS, PIPING AND VALVE
 ARRANGEMENT. COMPLY WITH FBC PL SECTION 712. PER FBC PL
 712.2, A CHECK VALVE AND A FULL OPEN VALVE SHALL BE
 LOCATED IN THE DISCHARGE LINE FROM THE SUMP AND SHALL
 BE ACCESSIBLE. ADDITIONALLY, INDICATE THE PUMP
 DISCHARGE GPM SHOWING IT IS CAPABLE OF DISCHARGING THE
 COMBINED STORM WATER AND A/C CONDENSATE ENTERING THE
 PIT.
  
 17. MP-2: TAG NOTE 4: REFERS TO B1-424 FOR ADDITIONAL
 INFORMATION. PER WPB FBC 107.2.1, PROVIDE REFERENCED
 DRAWING
  
 18. MP-4: NOTE 3: PER FBC PL 607.1, PROVIDE HOT WATER
 AND COLD WATER
  
 19. MP-4: NOTE 11: PER FBC PL 712.2, A CHECK VALVE AND
 A FULL OPEN VALVE SHALL BE LOCATED IN THE DISCHARGE
 LINE FROM THE SUMP AND SHALL BE ACCESSIBLE.
  
 20. MP-4: NOTE 10: PROVIDE DETAIL(S) FOR UTILITIES
 CONNECTION(S) OR DISPOSAL POINTS
  
 21. MP-4: PROVIDE NOTE FOR SUMP DISCHARGE CONNECTION TO
 BUILDING DRAIN ?PER FBC PL 712.3.5, PUMPS CONNECTED TO
 THE DRAINAGE SYSTEM SHALL CONNECT TO A BUILDING SEWER,
 BUILDING DRAIN, SOIL STACK, WASTE STACK OR HORIZONTAL
 BRANCH DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE
 MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING AND SUCH WYE FITTING SHALL BE LOCATED NOT LESS
 THAN 10 PIPE DIAMETERS FROM THE BASE OF ANY SOIL STACK,
 WASTE STACK OR FIXTURE DRAIN.?
  
 22. MP-5: NOTE 4; PER FBC PL 607.1, PROVIDE HOT WATER
 AND COLD WATER
  
 23. MP-6: ADD TO NOTE 8, ?VENT TERMINALS EXTENDING
 THROUGH THE WALL SHALL COMPLY WITH FBC PL 903.6?
  
 24. MP-8: STORM DRAIN PIPING AT FD; REPLACE P-TRAP WITH
 QUARTER BEND SWEEP. SEE FBC PL 1002.3, 1101.6 AND
 1103.1
  
 25. MP-8: PROVIDE AN INDIVIDUAL VENT FOR P-4 SERVICE
 SINK. SHOW COMPLIANCE WITH FBC PL 909.1 AND 1002.3(5)
  
 26. MP-8: P-1 WATER CLOSET IS A WALL HUNG FIXTURE. PER
 WPB FBC 107.2.1, SHOW IN THE SANITARY RISER AS ABOVE
 FLOOR WALL CONNECTION.
  
 27. MP-8: STORM RISER; PER WPB FBC 107.2.1, INCLUDE
 STORM DISCHARGE PIPING FROM SUMP.
  
 28. MP-8: PROVIDE NOTE FOR PUMP DISCHARGE CONNECTION TO
 BUILDING DRAIN ?PER FBC PL 712.3.5, PUMPS CONNECTED TO
 THE DRAINAGE SYSTEM SHALL CONNECT TO A BUILDING SEWER,
 BUILDING DRAIN, SOIL STACK, WASTE STACK OR HORIZONTAL
 BRANCH DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE
 MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING AND SUCH WYE FITTING SHALL BE LOCATED NOT LESS
 THAN 10 PIPE DIAMETERS FROM THE BASE OF ANY SOIL STACK,
 WASTE STACK OR FIXTURE DRAIN.?
  
 29. MP-8: PROVIDE HOT WATER ROUTING OR TANKLESS WATER
 HEATERS FOR P-3, P-4 IN WATER RISER BELOW P-2. IF
 PROVIDING ROUTING, SPECIFY TANKLESS HEATER THAT WILL
 ACCOMMODATE P-2, P-3 AND P-4.
  
 30. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 31. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC
 FOR EACH SYSTEM TO INCLUDE PIPE, VALVES, FITTINGS AND
 JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6, 7, 9 AND 11.
 ?A) ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
 ?B) DISCHARGE PIPING FROM SUMP PUMPS SHALL BE PRESSURE
 RATED IN ACCORDANCE WITH FBC PL SECTIONS 712.3.3.1 AND
 712.3.3.2, PROVIDE NOTE ON PLANS STATING THE SAME.
  
 32.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR HOT
 WATER PIPING AND CONDENSATE PIPING INSULATION
  
 33. MORE INFORMATION IS REQUIRED REGARDING THE STORM
 DRAIN. WHAT IS THE PURPOSE? IS THIS IN AN OPEN AREA
 SUBJECT TO RAINFALL?
 ?A) PER WPB FBC 107.2.1, CLARIFY. ADDITIONALLY, PROVIDE
 CALCULATIONS FOR SIZING THE GRAVITY DRAIN COMPLYING
 WITH FBC PL TABLES 1106.2 AND 1106.3.
 ?B) NOTE THE REQUIRED SLOPE FOR THE HORIZONTAL PIPING.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
 21100652 401 CLEMATIS ST
  
  
  
2021-11-12 07:09:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21100652 401 CLEMATIS ST
  
 1ST REVIEW
 PLUMBING COMMENTS:
 1.GENERAL NOTE: DEFERRED SUBMITTALS FBC 107.3.4.1
 REGARDING THE SUMP PUMP, POINT OF USE WATER HEATERS,
 ETC., DEFERRED SUBMITTALS IN THE FORM OF MANUFACTURERS
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS MAY BE
 SUBMITTED IN ACCORDANCE WITH WPB FBC 107.3.4.1 DEFERRED
 SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THEY SHALL
 BE SUBMITTED TO, APPROVED BY THE BUILDING OFFICIAL AND
 ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN
 RISK.
 BY PROVIDING THE NOTE ABOVE ON THE CONSTRUCTION
 DOCUMENTS TO BE REVIEWED AND LISTING THE ITEMS TO BE
 DEFERRED, YOU MAY PROCEED IN THIS MANNER.
  
 2.A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 THE RESTROOM DOES NOT APPEAR TO COMPLY WITH FBC ACC
 CHAPTERS 2, 3 AND 6. PER WPB FBC 107.2.1, CLARIFY.
 PLEASE REVIEW FBC ACC 203.9, 213.1. PROVIDE ELEVATIONS
 AND PLAN VIEW SHOWING COMPLIANCE WITH FBC ACC AS
 FOLLOWS AND IS APPLICABLE.
 ?A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 ?B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 ?C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ?D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ?E) FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 ?F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 ?G) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 ?H) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
 ?I) PER FBC ACC 604.8.1.2 AND 604.8.1.7, THE DOOR TO
 THE ACCESSIBLE TOILET RM/COMPARTMENT SHALL BE LOCATED
 IN THE FRONT PARTITION OR IN THE SIDE WALL OR PARTITION
 FARTHEST FROM THE WATER CLOSET, DIAGONAL TO THE WATER
 CLOSET.
 ?J)LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 ?K) PLEASE NOTE WHERE SINKS ARE PROVIDED, AT LEAST 5
 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606
 PER FBC ACC 212.3. DOES NOT APPLY TO A SERVICE SINK.
 ?L) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ?M) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 ?N) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
 ?O) SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1
 OR 304.3.2.
  
 3.PER WPB FBC 107.2.1, PROVIDE OCCUPANCY TYPE AND
 OCCUPANCY LOAD FOR STRUCTURE. PROVIDE FIXTURE SCHEDULE
 LISTING REQUIRED PLUMBING FIXTURES AND QUANTITIES
 REQUIRED BY FBC PL TABLE 403.1 TO ACCOMMODATE THE
 STATED OCCUPANCY AND OCCUPANCY LOAD.
  
 4. PER WPB FBC 107.2.1, PROVIDE AN OVERALL FLOOR PLAN
 FOR EACH LEVEL SHOWING RESPECTIVE LOCATIONS OF PIER 6
 AND PIER 7 AS WELL AS COMPREHENSIVE ELEVATION VIEW(S)
 IDENTIFYING THE LEVELS.
  
 5. MP-1: PER WPB FBC 107.2.1, SPECIFY A CARRIER SYSTEM
 FOR P-1 WATER CLOSET; PROVIDE MANUFACTURERS
 SPECIFICATION/INSTALLATION MANUAL FOR CARRIER SYSTEM
 FOR P-1 WATER CLOSET OR LIST AS A DEFERRED SUBMITTAL IN
 ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1.
  
 6. PER WPB FBC 107.2.1, PROVIDE MANUFACTURERS
 SPECIFICATION/INSTALLATION MANUAL FOR CARRIER FOR P-2
 LAVATORY OR LIST AS A DEFERRED SUBMITTAL IN ACCORDANCE
 WITH FBC 107.3.4.1; SEE COMMENT #1.
  
 7. MP-1: FIXTURE SCHEDULE P-4 SERVICE SINK; PER WPB FBC
 107.2.1, PROVIDE SUMP PUMP AND BASIN DETAIL SHOWING
 PIPING AND VALVE ARRANGEMENT SHOWING COMPLIANCE WITH
 FBC PL SECTION 712. PER FBC PL 712.2, A CHECK VALVE AND
 A FULL OPEN VALVE SHALL BE LOCATED IN THE DISCHARGE
 LINE FROM THE SUMP AND SHALL BE ACCESSIBLE.
  
 8. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR SUMP PUMP OR LIST AS A DEFERRED SUBMITTAL IN
 ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1.
  
 9. MP-1: FIXTURE SCHEDULE P-4 SERVICE SINK; A VACUUM
 BREAKER IS REQUIRED ON THE FAUCET HOSE THREADS PER FBC
 PL 608.1 AND 608.2. PER WPB FBC 107.2.1, SPECIFY AND
 ADD TO P-4 DESCRIPTION.
  
 10. PER WPB FBC 107.2.1, PROVIDE TANKLESS WATER HEATER
 INSTALLATION DETAIL SHOWING PIPING AND VALVE
 ARRANGEMENT.
  
 11. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR THE WATER HEATERS OR LIST AS A DEFERRED
 SUBMITTAL IN ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT
 #1.
  
 12. MP-1: FIXTURE SCHEDULE P-2 LAVATORY; FBC PL 419.5
 REQUIRES COLD OR TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 ?A) PER WPB FBC 107.2.1, PLEASE CLARIFY IF THERE IS TO
 BE PUBLIC ACCESS TO THE RESTROOM. COMPLIANT TEMPERED
 WATER DEVICES MAY BE PROVIDED IN ANY CASE BUT SHALL BE
 PROVIDED IF PUBLIC.
 ?B) PER WPB FBC 107.2.1, A SPECIFICATION WOULD BE
 REQUIRED.
  
 13. P-3 SINK AND P-4 SINK IN RISER BELOW P-2 LAVATORY,
 PER FBC PL 607.1, PROVIDE HOT WATER.
  
 14. PROVIDE DETAIL FOR HB-1 WALL BOX AND SHUTOFF VALVE.
 WILL WALL BOX BE RECESSED INTO STRUCTURE?
  
 15. PROVIDE MANUFACTURERS SPECIFICATION/INSTALLATION
 MANUAL FOR THE WALL BOX OR LIST AS A DEFERRED SUBMITTAL
 IN ACCORDANCE WITH FBC 107.3.4.1; SEE COMMENT #1.
  
 16. MP-2: TAG NOTE 1: SUMP PIT AND PUMP BY OTHERS; PER
 WPB FBC 107.2.1, PROVIDE DETAIL FOR SUMP PIT AND PUMP
 BY OTHERS SHOWING DIMENSIONS, PIPING AND VALVE
 ARRANGEMENT. COMPLY WITH FBC PL SECTION 712. PER FBC PL
 712.2, A CHECK VALVE AND A FULL OPEN VALVE SHALL BE
 LOCATED IN THE DISCHARGE LINE FROM THE SUMP AND SHALL
 BE ACCESSIBLE. ADDITIONALLY, INDICATE THE PUMP
 DISCHARGE GPM SHOWING IT IS CAPABLE OF DISCHARGING THE
 COMBINED STORM WATER AND A/C CONDENSATE ENTERING THE
 PIT.
  
 17. MP-2: TAG NOTE 4: REFERS TO B1-424 FOR ADDITIONAL
 INFORMATION. PER WPB FBC 107.2.1, PROVIDE REFERENCED
 DRAWING
  
 18. MP-4: NOTE 3: PER FBC PL 607.1, PROVIDE HOT WATER
 AND COLD WATER
  
 19. MP-4: NOTE 11: PER FBC PL 712.2, A CHECK VALVE AND
 A FULL OPEN VALVE SHALL BE LOCATED IN THE DISCHARGE
 LINE FROM THE SUMP AND SHALL BE ACCESSIBLE.
  
 20. MP-4: NOTE 10: PROVIDE DETAIL(S) FOR UTILITIES
 CONNECTION(S) OR DISPOSAL POINTS
  
 21. MP-4: PROVIDE NOTE FOR SUMP DISCHARGE CONNECTION TO
 BUILDING DRAIN ?PER FBC PL 712.3.5, PUMPS CONNECTED TO
 THE DRAINAGE SYSTEM SHALL CONNECT TO A BUILDING SEWER,
 BUILDING DRAIN, SOIL STACK, WASTE STACK OR HORIZONTAL
 BRANCH DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE
 MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING AND SUCH WYE FITTING SHALL BE LOCATED NOT LESS
 THAN 10 PIPE DIAMETERS FROM THE BASE OF ANY SOIL STACK,
 WASTE STACK OR FIXTURE DRAIN.?
  
 22. MP-5: NOTE 4; PER FBC PL 607.1, PROVIDE HOT WATER
 AND COLD WATER
  
 23. MP-6: ADD TO NOTE 8, ?VENT TERMINALS EXTENDING
 THROUGH THE WALL SHALL COMPLY WITH FBC PL 903.6?
  
 24. MP-8: STORM DRAIN PIPING AT FD; REPLACE P-TRAP WITH
 QUARTER BEND SWEEP. SEE FBC PL 1002.3, 1101.6 AND
 1103.1
  
 25. MP-8: PROVIDE AN INDIVIDUAL VENT FOR P-4 SERVICE
 SINK. SHOW COMPLIANCE WITH FBC PL 909.1 AND 1002.3(5)
  
 26. MP-8: P-1 WATER CLOSET IS A WALL HUNG FIXTURE. PER
 WPB FBC 107.2.1, SHOW IN THE SANITARY RISER AS ABOVE
 FLOOR WALL CONNECTION.
  
 27. MP-8: STORM RISER; PER WPB FBC 107.2.1, INCLUDE
 STORM DISCHARGE PIPING FROM SUMP.
  
 28. MP-8: PROVIDE NOTE FOR PUMP DISCHARGE CONNECTION TO
 BUILDING DRAIN ?PER FBC PL 712.3.5, PUMPS CONNECTED TO
 THE DRAINAGE SYSTEM SHALL CONNECT TO A BUILDING SEWER,
 BUILDING DRAIN, SOIL STACK, WASTE STACK OR HORIZONTAL
 BRANCH DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTION SHALL BE
 MADE THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING AND SUCH WYE FITTING SHALL BE LOCATED NOT LESS
 THAN 10 PIPE DIAMETERS FROM THE BASE OF ANY SOIL STACK,
 WASTE STACK OR FIXTURE DRAIN.?
  
 29. MP-8: PROVIDE HOT WATER ROUTING OR TANKLESS WATER
 HEATERS FOR P-3, P-4 IN WATER RISER BELOW P-2. IF
 PROVIDING ROUTING, SPECIFY TANKLESS HEATER THAT WILL
 ACCOMMODATE P-2, P-3 AND P-4.
  
 30. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 31. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC
 FOR EACH SYSTEM TO INCLUDE PIPE, VALVES, FITTINGS AND
 JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6, 7, 9 AND 11.
 ?A) ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
 ?B) DISCHARGE PIPING FROM SUMP PUMPS SHALL BE PRESSURE
 RATED IN ACCORDANCE WITH FBC PL SECTIONS 712.3.3.1 AND
 712.3.3.2, PROVIDE NOTE ON PLANS STATING THE SAME.
  
 32.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR HOT
 WATER PIPING AND CONDENSATE PIPING INSULATION
  
 33. MORE INFORMATION IS REQUIRED REGARDING THE STORM
 DRAIN. WHAT IS THE PURPOSE? IS THIS IN AN OPEN AREA
 SUBJECT TO RAINFALL?
 ?A) PER WPB FBC 107.2.1, CLARIFY. ADDITIONALLY, PROVIDE
 CALCULATIONS FOR SIZING THE GRAVITY DRAIN COMPLYING
 WITH FBC PL TABLES 1106.2 AND 1106.3.
 ?B) NOTE THE REQUIRED SLOPE FOR THE HORIZONTAL PIPING.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
 21100652 401 CLEMATIS ST
  
  
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 NOTE: PER WPB FBC 105.1, A PLUMBING SUB-PERMIT IS
 REQUIRED.
  
 1.NEW COMMENT: FALLS UNDER THE RULES OF THE FAIR
 HOUSING ACT. IN ACCORDANCE WITH WPB FBC 107.2.1,
 INDICATE ON THE FLOOR PLAN, COMPLIANCE WITH THE FAIR
 HOUSING ACT, INDICATING TYPE OF BATHROOM(S), (TYPE A,
 TYPE B), IN ACCORDANCE WITH GUIDELINES UNDER
 REQUIREMENT 7, INCLUDING CLEAR FLOOR SPACE AND
 MANEUVERING. ALTERNATIVELY YOU MAY SUBMIT A REQUEST FOR
 WAIVER IN THE FORM OF A LETTER SHOWN BELOW. THIS SHOULD
 BE SIGNED BY BOTH PARTIES (DESIGNER AND OWNER), BUT
 ONLY THE OWNER?S SIGNATURE NEEDS TO BE NOTARIZED.
  
 PROJECT ADDRESS: ______________________________________
 _____________________
 PERMIT NUMBER: ________________________
 THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE
 PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS
 OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER
 AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF
 SALE IF SO REQUESTED BY THE BUYER.
  
 SIGNATURE OF DESIGNER: ______________________________
 PRINTED NAME OF DESIGNER: ___________________________
  
 SIGNATURE OF OWNER: ________________________________
 PRINTED NAME OF OWNER: _____________________________
 NOTARY FOR OWNER?S SIGNATURE:
 STATE OF FLORIDA, COUNTY OF PALM BEACH
 THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME
 THIS _____ DAY OF ________, 20__ BY
 ___________________________ WHO IS PERSONALLY KNOWN TO
 ME OR WHO HAS PRODUCED: ___________________________ AS
 IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH.
 NOTARY SIGNATURE ___________________________________
 NOTARY PRINTED NAME ________________________________
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED
 WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE
 NUMBER IN ACCORDANCE WITH WPB FBC 107.2.1, A PAPER PLAN
 WITH WET SIGNATURE SHALL BE PROVIDED TO THE BUILDING
 DEPARTMENT FOR HARD RECORD FILE PRIOR TO ISSUANCE OF A
 PERMIT.
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED
 WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE
 NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.2, A PAPER
 PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE
 BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO
 ISSUANCE OF A PERMIT.
  
 PHONE 561-805-6715
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 PLUMBING COMMENTS: APPROVED WITH PROVISO
  
  
 PLUMBING COMMENTS: DENIED
  
 PER WPB FBC 107.1,ALL PLANS TO BE SIGNED AND SEALED BY
 THE DESIGNER IN ACCORDANCE WITH FAC AND FS. DESIGNER TO
 PROVIDE DIGITAL SIGNATURE IN ACCORDANC WITH FAC AND FS
 OR SHALL PROVIDE SIGNED AND SEALED PAPER DOCUMENT PRIOR
 TO PERMIT ISSUANCE.CALL 561-805-6724 FOR ADDITIONAL
 INFORMATION
 SEE WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE
 CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE
 LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY
 ONE INDIVIDUAL, THEY WOULD HAVE TO BE LICENSED AS A
 BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT
 ALL THESE TRADES UNDER ONE SHEET.
  
 1.PLEASE REFER TO BUILDING PLANS EXAMINER?S COMMENTS:
 1) THE BUILDING CONTRACTOR HAS NOT TAKEN RESPONSIBILITY
 FOR THE DESIGN/ CREATION OF THE FLOOR PLAN AND KITCHEN
 ELEVATION PLANS. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
  
 A COMPREHENSIVE
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING
 PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR
 THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE.
  
 CONTRACTOR AS DESIGNER) THE FLOOR PLAN WAS NOT DESIGNED
 BY EITHER AN ENGINEER OR ARCHITECT. CERTIFICATION BY
 CONTRACTOR. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR.
  