Plan Review Notes
Plan Review Notes For Permit 21100610
Permit Number 21100610
Review Stop E
Sequence Number 2
Notes
Date Text
2022-01-06 18:57:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTES STATE LOAD IS BEING REDUCED. AN ACCURATE LOAD
 CALCULATION MUST BE PROVIDED REGARDLESS THAT LOAD IS
 BEING REDUCED. FBC 107.2.1 NEC 220
  
 2. NO INFORMATION SHOWN ON EXISTING SERVICE SIZE??? FBC
 107.2.1
  
 3. NO PANEL SCHEDULES PROVIDED AS PER PREVIOUS PLAN
 REVIEW COMMENTS. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  
2021-12-08 13:57:05WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21100610
 ADD: 8851 IBIS BLVD./ GUARDHOUSE RENOVATION
 CONT: ANDERSON-MOORE CONSTRUCTION GROUP
 TEL: 561-348-4805
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. DEC. 08TH/2021
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET A-2 THE FLOOR PLAN DOES NOT
 APPEAR TO TAKE INTO CONSIDERATION FOR UPGRADING THE
 GUARDHOUSE FOR ACCESSIBILITY.
 2020 FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS LISTED FOR EACH
 ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE
 ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST
 OF THE 2020 ACCESSIBILITY CODE. $265,000.00 X 0.20 =
 $53,000.00 DOLLARS.
  
 202.4.2 ACCESSIBILITY FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF THE ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREAS FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COST. IN
 CHOOSING WHICH ELEMENTS TO PROVIDE, PRIORITY SHOULD BE
 GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE GREATEST
 ACCESS, IN THE FOLLOWING ORDER: (I) AN ACCESSIBLE
 ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA;
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM; (IV) ACCESSIBLE TELEPHONES:
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND (VI) WHEN
 POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH AS
 PARKING, STORAGE, AND ALARMS.
  
 1A) 2ND REQUEST. THE FLOOR PLAN DOES NOT INDICATE WHICH
 ENTRANCE WILL SHOW COMPLIANCE FOR AN ACCESSIBLE
 ENTRANCE2020 FBC-ACCESS. CODE CHANGES IN LEVEL 303.2
 AND 303.3. WHERE CHANGES IN LEVEL ARE PERMITTED IN THE
 FLOOR OR GROUND SURFACES, THEY SHALL COMPLY WITH
 SECTION 303. SEE 303.1 & 303.2.
  
 1B) 2ND REQUEST. THE FLOOR PLAN WILL NEED TO SHOW HOW
 THE BATHROOM WILL MEET COMPLIANCE WITH THE
 ACCESSIBILITY CODE CHAPTER 6 FOR SECTIONS 603-609.
 2020 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 2020 FBC-ACCESSIBILITY CODE 608.2.1 AND FIGURE 608.2.1
 MISSING THE 36 X 48 SHOWER CLEAR FLOOR SPACE WITH ONE
 FOOT BACK OF THE SEAT WALL.
  
 1C) 2ND REQUEST NOTE D NOTED, PART OF THE 20 %
 DISPROPORTIONATE COST. THE EMPLOYEES BREAK ROOM AND
 COMPLIANCE WITH 606 LAVATORIES AND SINKS> 2020
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. LAVATORIES
 AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 1D) COMPLIED.
  
 1E) 2ND REQUEST. PART OF THE 20% DISPROPORTIONATE COST.
 GUARD HOUSE NOTE D EXISTING CABINETS TO REMAIN NEW
 COUNTER TOPS. 902.1. DINING SURFACES AND WORK SURFACES
 SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1
 GENERAL. WORK AREA EXAMPLES OF WORK SURFACES INCLUDE
 WRITING SURFACES, STUDY CARRELS, STUDENT LABORATORY
 STATIONS, AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ADA
 SCOPING PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 2-4) COMPLIED.
  
 5-8) BUILDING PROVISO/ DEFERRED SUBMITTALS
 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, & MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 6) DEFERRED SUBMITTALS. W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING (SHOP DRAWING STAMP OF
 APPROVAL) BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) DEFERRED SUBMITTALS. IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY IN THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 8A) DEFERRED SUBMITTALS. 107.2.1.2 FOR ROOF ASSEMBLIES
 REQUIRED BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, VENTING, FASTENING REQUIREMENTS,
 FLASHING REQUIREMENTS AND WIND RESISTANCE RATING THAT
 ARE REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 8B) DEFERRED SUBMITTALS. FOR CONCRETE OR CLAY TILE
 ROOFING THE 2020 FBC-BUILDING CODE SECTION 1507.3.8
 RECOGNIZES 6TH EDITION OF THE FRSA FLORIDA HIGH WIND
 CONCRETE AND CLAY TILE MANUAL AND REQUIREMENTS WITHIN,
 INCLUDING UNDERLAYMENT REQUIREMENTS, FLASHINGS, BATTEN
 INSTALLATION, RIDGE AND HIP ATTACHMENT METHODS
 MECHANICAL, ADHESIVE SET OR MORTAR SET ATTACHMENT
 METHODS.
  
 9) DEFERRED SUBMITTALS. FOR LOADING FOR THE TRUSSES,
 UPLIFT LOADS, PARALLEL LOADS NOR GRAVITY LOADS.
  
 10A) SHEET A-7 WALL DETAIL 1 INDICATES THE USE OF SPRAY
 FOAM INSULATION W/ FIRE BARRIER ABOVE THE CEILING.
 PLEASE PROVIDE THE MANUFACTURES REPORT (ICC ER OR ERS
 REPORT) WITH LIMITATIONS. NOTE PLEASE CIRCLE WHICH
 SYSTEM WILL BE USED IN THE SPRAY FOAM INSTALLATION.
  
 10B) PLEASE BE AWARE OF THE REQUIREMENT IN THE 2020
 FBC-B FOR AN IGNITION BARRIER IN COMPLIANCE WITH
 SECTION 2603.4.1.6.
  
 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  