Plan Review Notes
Plan Review Notes For Permit 21100610
Permit Number 21100610
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-10-19 14:43:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE APPEARS TO A 12' WIDTH DIMENSION FOR THE
 ENTRANCE & EXIT.
  
 THE MINIMUM WIDTH FOR A FIRE LANE AND FD ACCESS IS 20'.
 LESSER DIMEENSION MAY BE APPROVED BY THE AHJ.
  
 12' IS TOO NARROW AND THE RISK OF DAMAGE TO THE
 STRUCTURES & APPARATUS MAY OCCUR AND NEEDS TO BE
 INCREASED.
  
 PLEASE REIVEW AND PROVIDE GREATER DETAIL OF THE
 EXISTING ENTRANCE & EXIT AND HOW THE FD CURRENTLY
 ACCESSES THROUGH.
  
 FOR CLARIFICATION, PLEASE PROVIDE HOW THE PROPOSED IS
 EQUAL OR IMPROVES THE EXISTING SETUP.
  
  
  
 1A) IS THIS A 24 HOUR ATTENDED SECURITY FOR 24HR FD
 ACCESS OR IS A KNOX KEY SWITCH EXISTING AND WILL BE
 PROVIDE WITH THE PROPOSED?
  
 PLEASE PROVIDE DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  