2021-10-19 14:43:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE APPEARS TO A 12' WIDTH DIMENSION FOR THE | | ENTRANCE & EXIT. | | | | THE MINIMUM WIDTH FOR A FIRE LANE AND FD ACCESS IS 20'. | | LESSER DIMEENSION MAY BE APPROVED BY THE AHJ. | | | | 12' IS TOO NARROW AND THE RISK OF DAMAGE TO THE | | STRUCTURES & APPARATUS MAY OCCUR AND NEEDS TO BE | | INCREASED. | | | | PLEASE REIVEW AND PROVIDE GREATER DETAIL OF THE | | EXISTING ENTRANCE & EXIT AND HOW THE FD CURRENTLY | | ACCESSES THROUGH. | | | | FOR CLARIFICATION, PLEASE PROVIDE HOW THE PROPOSED IS | | EQUAL OR IMPROVES THE EXISTING SETUP. | | | | | | | | 1A) IS THIS A 24 HOUR ATTENDED SECURITY FOR 24HR FD | | ACCESS OR IS A KNOX KEY SWITCH EXISTING AND WILL BE | | PROVIDE WITH THE PROPOSED? | | | | PLEASE PROVIDE DETAILS. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|