2022-03-25 18:19:19 | 2ND PRIVATE PROVIDER AUDIT FBC-2020 RESIDENTIAL |
| PERMIT-21100601 |
| |
| |
| BUILDING AUDIT RESULTS: DENIED. |
| |
| 1) COMPLIED. |
| |
| 2) WILL COMPLY. SEPARATE PERMITS ARE REQUIRED FOR THE |
| GENERATOR, DRIVEWAY, LANDSCAPING, ELEVATOR, LAWN |
| SPRINKLERS, POOLS, SITE WALLS AND FENCES. |
| |
| 3) COMPLIED. |
| |
| 4) NOT COMPLIED. [THE MAXIMUM DESIGN PRESSURES IN NEW |
| NOA NO. 20-1015.18 ARE +48 PSF AND -52 PSF. THIS DOES |
| NOT MEET THE -61.1 PSF REQUIRED NEGATIVE PRESSURE FOR |
| THE OPENING.]THE WIND PRESSURES FOR THE 9' GARAGE DOOR |
| ARE SPECIFIED ON SHEET S5.00 AS +47.2 PSF, -61.1 PSF. |
| THE MAXIMUM NEGATIVE PRESSURE ON THE PRODUCT APPROVAL |
| FOR THE GARAGE DOORS IS -60.3 PSF, WHICH IS LESS THAN |
| THE ENGINEER HAS SPECIFIED FOR THAT OPENING. FBC |
| 107.3.4 |
| |
| 5) COMPLIED. |
| |
| 6) COMPLIED. |
| |
| 7) NOT COMPLIED. [ THE WALL SECTION STILL SHOWS SOFFIT |
| VENTS AND THE INSULATION IS SHOWN AT THE CEILING AND |
| NOT UNDERNEATH THE ROOF SHEATHING. ] ON SHEET A3.2, THE |
| WALL SECTION SHOWS SPRAY FOAM INSULATION ON THE BOTTOM |
| CORD OF THE TRUSSES AND SOFFIT VENTS FOR THE ATTIC |
| SPACE. THE ENERGY EFFICIENCY FORM SPECIFIES AN UNVENTED |
| ATTIC. PLEASE CORRECT. FBC 107.2.1 |
| |
| 8) COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) COMPLIED. |
| |
| 11) NOT COMPLIED. [ I DID NOT SEE THAT THE WINDOW |
| SCHEDULE WAS CHANGED TO SPECIFY FIXED RATHER THAN |
| CASEMENT WINDOWS.] THE PRODUCT APPROVAL THAT WAS |
| SUBMITTED FOR THE KOLBE CASEMENT WINDOWS HAS A MAXIMUM |
| FRAME HEIGHT OF 72 INCHES (6 FT.) FOR THE HALF-ROUND |
| WINDOWS. THE WINDOW SCHEDULE ON SHEET A-3.3 HAS SOME |
| WINDOWS THAT ARE 108 INCHES (9 FT.) IN HEIGHT. SUBMIT |
| PRODUCT APPROVALS FOR THE 9 FT TALL KOLBE WINDOWS. FBC |
| 107.3.4 |
| |
| 12) NOT COMPLIED. [ I DID NOT SEE THAT THE WINDOW |
| SCHEDULE WAS CHANGED TO SPECIFY FIXED RATHER THAN |
| CASEMENT WINDOWS.] SUBMIT PRODUCT APPROVALS FOR THE |
| SIGNATURE BRAND 9 FT TALL "CEDAR" CASEMENT WINDOWS. FBC |
| 107.3.4 |
| |
| 13) COMPLIED. |
| |
| 14) COMPLIED. |
| |
| 15) PARTIALLY COMPLIED. [ I DID NOT SEE THE NOTE FOR |
| THE WATERPROOFING IN SECTION 3.2/S-1 ON SHEET A-3.2. ] |
| SPECIFY HOW THE FLOOR OF THE FRONT AND REAR BALCONIES |
| WILL BE WATERPROOFED. FBC 107.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |