2022-03-25 18:19:192ND PRIVATE PROVIDER AUDIT FBC-2020 RESIDENTIAL
 PERMIT-21100601
  
  
 BUILDING AUDIT RESULTS: DENIED.
  
 1) COMPLIED.
  
 2) WILL COMPLY. SEPARATE PERMITS ARE REQUIRED FOR THE
 GENERATOR, DRIVEWAY, LANDSCAPING, ELEVATOR, LAWN
 SPRINKLERS, POOLS, SITE WALLS AND FENCES.
  
 3) COMPLIED.
  
 4) NOT COMPLIED. [THE MAXIMUM DESIGN PRESSURES IN NEW
 NOA NO. 20-1015.18 ARE +48 PSF AND -52 PSF. THIS DOES
 NOT MEET THE -61.1 PSF REQUIRED NEGATIVE PRESSURE FOR
 THE OPENING.]THE WIND PRESSURES FOR THE 9' GARAGE DOOR
 ARE SPECIFIED ON SHEET S5.00 AS +47.2 PSF, -61.1 PSF.
 THE MAXIMUM NEGATIVE PRESSURE ON THE PRODUCT APPROVAL
 FOR THE GARAGE DOORS IS -60.3 PSF, WHICH IS LESS THAN
 THE ENGINEER HAS SPECIFIED FOR THAT OPENING. FBC
 107.3.4
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) NOT COMPLIED. [ THE WALL SECTION STILL SHOWS SOFFIT
 VENTS AND THE INSULATION IS SHOWN AT THE CEILING AND
 NOT UNDERNEATH THE ROOF SHEATHING. ] ON SHEET A3.2, THE
 WALL SECTION SHOWS SPRAY FOAM INSULATION ON THE BOTTOM
 CORD OF THE TRUSSES AND SOFFIT VENTS FOR THE ATTIC
 SPACE. THE ENERGY EFFICIENCY FORM SPECIFIES AN UNVENTED
 ATTIC. PLEASE CORRECT. FBC 107.2.1
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) NOT COMPLIED. [ I DID NOT SEE THAT THE WINDOW
 SCHEDULE WAS CHANGED TO SPECIFY FIXED RATHER THAN
 CASEMENT WINDOWS.] THE PRODUCT APPROVAL THAT WAS
 SUBMITTED FOR THE KOLBE CASEMENT WINDOWS HAS A MAXIMUM
 FRAME HEIGHT OF 72 INCHES (6 FT.) FOR THE HALF-ROUND
 WINDOWS. THE WINDOW SCHEDULE ON SHEET A-3.3 HAS SOME
 WINDOWS THAT ARE 108 INCHES (9 FT.) IN HEIGHT. SUBMIT
 PRODUCT APPROVALS FOR THE 9 FT TALL KOLBE WINDOWS. FBC
 107.3.4
  
 12) NOT COMPLIED. [ I DID NOT SEE THAT THE WINDOW
 SCHEDULE WAS CHANGED TO SPECIFY FIXED RATHER THAN
 CASEMENT WINDOWS.] SUBMIT PRODUCT APPROVALS FOR THE
 SIGNATURE BRAND 9 FT TALL "CEDAR" CASEMENT WINDOWS. FBC
 107.3.4
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) PARTIALLY COMPLIED. [ I DID NOT SEE THE NOTE FOR
 THE WATERPROOFING IN SECTION 3.2/S-1 ON SHEET A-3.2. ]
 SPECIFY HOW THE FLOOR OF THE FRONT AND REAR BALCONIES
 WILL BE WATERPROOFED. FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  