2021-12-04 10:30:38 | PLAN REVIEW / NFIP |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| CITY ORDINANCE NO. 4658-16 |
| |
| 4TH REVIEW |
| RESULTS: FAILED |
| |
| RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE. |
| (CABANA/GARAGE) |
| |
| 1. SECTION A2. ADDRESS IS 7113 S FLAGLER DRIVE |
| |
| 2. SECTION A9 (A). DATA ENTERED IS 560 SF. PLAN PAGE |
| A-1.1 INDICATES GARAGE HAS 665 SF. |
| |
| 3. SECTION A9 (B). BASED ON PLAN PAGE A-1.1 AND |
| ALLOWING 200 SF PER VENT, 4 VENTS WILL BE REQUIRED. |
| |
| 4. SECTION A9 (C). ASSUMING FLOOD VENTS INSTALLED WILL |
| BE 8" X 16", IT IS CUSTOMARY TO ALLOT 128 SQ. IN. PER |
| VENT. |
| |
| 5. SECTION D, COMMENTS. INCLUDE TYPE AND MODEL NUMBER |
| OF FLOOD VENTS INSTALLED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| GENERAL INFORMATION: |
| |
| PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH BASE FLOOD |
| ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD. |
| MAIN DWELLING UNIT IS LOCATED IN FLOOD ZONE AE 7 . BFE |
| IS 7.0' NAVD. DFE SHALL NOT BE LESS THAN 9.0 FEET NAVD. |
| FREE STANDING CABANA/GARAGE IS LOCATED IN FLOOD ZONE AE |
| 6. BFE IS 6.0' NAVD. DFE SHALL NOT BE LESS THAN 8.0' |
| NAVD. |
| |
| |
| NOTICE: |
| |
| 3 ELEVATION CERTIFICATES (EC) ARE REQUIRED |
| |
| A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| REQUIRED AT TIME OF PERMIT APPLICATION. |
| |
| A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS |
| REQUIRED AT PLACEMENT OF 1ST FLOOR. |
| SUBMIT TO BUILDING DEPARTMENT FOR REVIEW. |
| |
| A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL |
| GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE |
| BUILDING. |
| |
| |
| NOTICE: A SEPERATE PERMIT AND ELEVATION CERTIFICATE ARE |
| REQUIRED FOR THE MAIN RESIDENCE. (SEE PERMIT 21060673) |
| |
| NOTICE: PROVISO ON PLAN PAGE S-1.1 |
| |
| NOTICE: PRINT HOLD FOR CONSTRUCTION DRAWING EC |
| |
| NOTICE: C/O HOLD FOR FINISHED CONSTRUCTION EC |
| |
| NOTICE: COMMENTS TO BE ADDED TO INSPECTION SCREEN AFTER |
| INSPECTION HOLDS REMOVED. |