Date |
Text |
2021-12-04 10:18:27 | BUILDING PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| 4TH REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: PLAN PAGE A-1.1 STATES GARAGE HAS 665 SF. |
| |
| 1. DESIGNER SHALL INDICATE ON ICC-ES REPORT THE MODEL |
| OF THE FLOOD VENTS TO BE INSTALLED. |
| THIS INFORMATION IS ALSO REQUIRED IN SECTION D, |
| COMMENTS, OF THE ELEVATION CERTIFICATE. (SEE NFIP |
| REVIEW) |
| FBC 107.3.4 PRODUCTS WHICH ARE REGULATED BY FAC RULE |
| 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. |
| |
| 2. PLAN PAGE A-1.1 INDICATES GARAGE HAS 665 SF. FLOOD |
| VENTS LISTED ON ELEVATION CERTIFICATE INDICATE EACH |
| VENT SHALL COVER 200SF. 4 FLOOD VENTS ARE REQUIRED. |
| REVISE PLAN PAGE A-1.1. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 3. INDICATE ON PLAN PAGE A-1.1 THE TYPE OF FLOOD VENTS |
| TO BE INSTALLED. THE LEGED "P" ON PLAN PAGE A-4.2 |
| STATES "FLOOD PANEL". |
| THIS INFORMATION IS ALSO REQUIRED IN SECTION D, |
| COMMENTS, OF THE ELEVATION CERTIFICATE. (SEE NFIP |
| REVIEW) |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |