Plan Review Notes
Plan Review Notes For Permit 21100553
Permit Number 21100553
Review Stop M
Sequence Number 3
Notes
Date Text
2022-06-28 08:30:37THE ORIGINAL SUBMITTAL OF THE MECHANICAL SYSTEM HAS
 ENERGY CALCS AND EQUIPMENT SIZING FOR A MINI-SPLIT FOR
 THIS NEW AREA. THE LATEST SUBMITTAL HAS A NEW
 MECHANICAL DRAWING SHOWING THE MINI-SPLIT BEING REMOVED
 AND A 10 INCH DUCT FROM THE AHU-1 GOING TO THE NEW WORK
 AREA. YOU WILL NEED TO UPDATE THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS TO SHOW THAT THE EXISTING UNIT IS
 SIZED TO HANDLE THE ADDITIONAL LOAD CREATED BY THE NEW
 AREA. FBC 107.2.1
  