2021-11-09 12:06:35 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| PERMIT- 21100553 |
| 11/9/21 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A COMPLETE PLUMBING REVIEW FOR THE PROJECT CANNOT BE |
| COMPLETED AT THIS TIME BECAUSE THE PLANS SHOW TWO |
| DWELLING UNITS ON THE SAME LOT WHICH WILL REQUIRE |
| SEPARATE PERMITS FOR EACH DWELLING UNIT. PLEASE SEE |
| COMMENTS UNDER THE ADDRESSING REVIEW. COMMENTS LISTED |
| BELOW WILL ADDRESS THE MAIN HOUSE AND THE DWELLING UNIT |
| SEPARATELY. |
| |
| 2) MAIN HOUSE- SHEET P1: |
| A) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. |
| B) TWO DWELLINGS ON THE SAME LOT WILL REQUIRE WATER |
| USERS TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE |
| POINT OF DELIVERY. A REDUCED PRESSURE ZONE (RPZ) |
| BACKFLOW DEVICE WILL BE REQUIRED FOR THE WATER METER |
| PER THE CITY OF WEST PALM UTILITIES DEPARTMENT AND |
| THEIR CROSS-CONNECTION CONTROL PROGRAM. |
| PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| 3) GUEST HOUSE- SHEET P1: |
| A) PROVIDE A CLEANOUT AT THE JUNCTION OF THE GUEST |
| HOUSE SANITARY LINE AND THE PROPERTY SEWER LINE SHOWN |
| BETWEEN THE TWO BUILDINGS- SECTION P3005.2.3 FBC RES. |
| B) PROVIDE A DRAIN FOR THE OUTDOOR SHOWER OR SHOW HOW |
| THE WATER WILL BE DRAINED AWAY FROM THE BUILDING TO AN |
| APPROVED PLACE OF DISPOSAL- SECTION P3001.1 FBC RES. |
| C) REFER TO TABLE C403.2.10 FBC EC.AND CORRECT THE |
| DRAWING TO INDICATE 1-INCH THICK HOT WATER PIPE |
| INSULATION WILL BE INSTALLED ON THE UNDERGROUND AND |
| ABOVE GROUND LINES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |