2021-11-09 13:38:22 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 21100553 |
| 11/9/21 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A COMPLETE GAS REVIEW FOR THE PROJECT CANNOT BE |
| COMPLETED AT THIS TIME BECAUSE THE PLANS SHOW TWO |
| DWELLING UNITS ON THE SAME LOT WHICH WILL REQUIRE |
| SEPARATE PERMITS FOR EACH DWELLING UNIT. PLEASE SEE |
| COMMENTS UNDER THE ADDRESSING REVIEW. COMMENTS LISTED |
| BELOW WILL ADDRESS THE MAIN HOUSE AND THE DWELLING UNIT |
| SEPARATELY. |
| |
| 2) MAIN HOUSE- SHEET G1: |
| A) PLEASE REVISE THE DRAWINGS TO SHOW THE GAS PIPING TO |
| THE GUEST HOUSE REMOVED FROM THE MAIN HOUSE SYSTEM AND |
| METER. THE GAS PIPING FOR THE GUEST HOUSE WILL BE |
| SUPPLIED BY A SEPARATE METER. |
| B) PLEASE REVISE THE RISER TO INDICATE THE TYPE AND |
| SIZE OF PIPING FROM THE METER TO THE RANGE AND LOCATION |
| OF THE LOW PRESSURE REGULATOR, IT APPEARS THAT 1/2-INCH |
| SCHEDULE 40 METALLIC WILL BE INSTALLED FROM THE METER |
| TO THE LOW PRESSURE REGULATOR, AND FROM THE REGULATOR |
| TO THE RANGE- PLEASE PROVIDE A CLEAR RISER DRAWING- |
| SECTIONS 107.2.1 & 107.3.5.3 WPB. |
| C) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE |
| AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION- |
| G2407.1 FBC RES. |
| |
| 3) GUEST HOUSE: |
| A) PROVIDE A SEPARATE RISER DRAWING FOR THE GAS PIPING |
| AT THE GUEST HOUSE-- SECTIONS 107.2.1 & 107.3.5.3 WPB. |
| B) PLEASE CONTACT FLORIDA PUBLIC UTILITIES (FPU) |
| CONCERNING INSTALLATION OF THE SEPARATE GAS METER- |
| 1-800-427-7712. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |