2021-12-29 11:04:14 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21100553 |
| |
| NOTE: |
| ADDITION SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| NOTE: |
| CHANGE OF OCCUPANCY (GARAGE CONVERSION)SEC. 605 AND |
| SEC. 1001.2.1, SEC. 604 AND SEC. 901.2, SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW WORK SHALL COMPLY WITH |
| THE MATERIALS AND METHODS REQUIREMENTS IN THE FLORIDA |
| BUILDING CODE. |
| |
| 1- THERE ARE TWO SEPARATE STRUCTURES IN THIS PROPERTY. |
| A PERMIT APPLICATION IS REQUIRED FOR EACH STRUCTURE. |
| PLEASE SUBMIT A SEPARATE PERMIT APPLICATION FOR THE |
| SEPARATE GARAGE/GUEST SUITE BUILDING. SAME PLANS CAN BE |
| USED. SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE |
| INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS |
| RETENTION. SEC. 107.2.1.3 CITY AMENDMENTS. |
| |
| 2- LOT DRAINAGE |
| PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY |
| AMENDMENTS. |
| SEC. 110.9 CITY AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| 3- GARAGE CONVERSION. ENTRY DOOR DOESN'T COMPLY WITH |
| THE MIN. CLEAR WIDTH OF 32" AS REQUIRED BY SEC. R311.2 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| 4- REVISE DESIGN CRITERIA ON SHEET S.0. FBC 2020 HAS |
| ADOPTED THE ASCE 7-16 NOT 7-10. |
| ALSO, REVISE THE PROJECT DATA INFORMATION ON SHEET T1. |
| FBC-2020 IS THE 7TH EDITION NOT THE 6TH EDITION. SEC. |
| 553 F.S. |
| |
| 5- PROVIDE STRUCTURAL BUCK DETAIL FOR ALL DOOR TYPES |
| AND WINDOWS SHOWING COMPLIANCE WITH SEC. R609.7.2.1 |
| FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND |
| FASTENING. |
| NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| THE DOOR/WINDOW FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| FBC-RESIDENTIAL. |
| |
| 6- SHEET S.2: |
| A)REVISE ROOF PLAN NOTE #1: REVISE PLYWOOD ROOF |
| SHEATHING NAILING SPACING. ROOF SHEATHING NEEDS TO BE |
| NAILED WITH RING SHANK NAILS AT 4 INCHES O.C. IN THE |
| FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND |
| TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| NOTE: REVISE ALL NOTES REFERENCING THE ROOF SHEATHING |
| THICKNESS AND NAIL SIZE/ SPACING SHOWN ON DRAWINGS |
| SUBMITTED TO AVOID CONFLICTS/DELAYS. |
| |
| B)REVISE EDGE DISTANCE "A" SHOWN ON THE ROOF DIAGRAMS. |
| DIMENSION FOR "A" NEEDS TO BE 4'-0" MIN. ON ALL CASES |
| AS REQUIRED BY NOTE ON FIGURE R301.2(7). |
| |
| 7- ROOFING: |
| A)PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE |
| NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001 |
| |
| B)SPECIFY SHINGLES ROOF PITCH. NEED TO VERIFY |
| COMPLIANCE WITH SEC. R905.2.2 FBC-RESIDENTIAL. |
| |
| 8- ENERGY CALCULATIONS: |
| A)NEED A SEPARATE PERMIT APPLICATION FOR EACH SEPARATE |
| STRUCTURE. |
| SEC. R101.3 FBC-ENERGY CONSERVATION. SEC. |
| R101.5FBC-ENERGY CONSERVATION. |
| NOTE: GARAGE ENERGY CALCULATIONS NEED TO BE FOR ENTIRE |
| BUILDING (EXISTING AND ADDITION) SINCE IT WAS NOT A/C |
| BEFORE. |
| |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S NAME AND BUILDER'S NAME. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| C)ITEM #5 ON PAGE 1 SPECIFIES NO WORST CASE SCENARIO, |
| WHILE PAGE 2 SHOWS A ROTATION OF 270 DEGREES. ENERGY |
| CALCULATIONS NEED TO BE SITE SPECIFIC AS REQUIRED BY |
| SEC. R405.4.2.1 (4) FBC- ENERGY CONSERVATION. REVISE AS |
| REQUIRED. |
| |
| D)REVISE WINDOWS ORIENTATION, AREA AND OVERHANG DEPTH |
| AND SEPARATION TO MATCH PLANS. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| 9-DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVAL AS |
| REQUIRED BY FAC 61G20-3.001 FOR: |
| (NOTE:ALL PRODUCT APPROVALS TO BE APPROVED IN WRITING |
| BY DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| A)EXTERIOR DOORS. |
| B)WINDOWS. |
| C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO AVOID DELAYS/CONFLICTS). |
| D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| E)ROOF SHINGLES. |
| F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |