Plan Review Notes For Permit 21100511 |
Permit Number |
21100511 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-17 10:58:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE INFORMATION A DRWING SUBMITTED IS VERY GENERAL | | AND VAGUE AS TO WHAT IS BEING PROPOSED. | | | | PLEASE PROVIDE GREATER DETAIL, INCLUDING ANY PROPOSED | | DEMO, WHAT IS EXISTING AND THEN WHAT IS NEW. | | | | | | 1A) THERE IS NO INDICATION OF ANY FIRE SPRINKLER HEADS | | NOR FIRE ALARM EQUIPMENT WITHIN THE PROPOSED AREA. | | | | PLEASE PROVIDE DETAILS. | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | DRAWINGS. | | | | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE | | OF ACKNOWLEDGMENT. | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|