2022-01-19 14:30:51FBC-2020 PLUMBING AUDIT
 PERMIT- 21100388
 1/19/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 AUDIT RESULTS:
  
 1) SHEET P1.0 P1.1: THE PLANS DO NOT CLARIFY IF THE
 RECREATIONAL FACILITIES AND SWIMMIMG POOL AT 445 DATURA
 ARE FOR USE BY THE GENERAL PUBLIC OR EXCLUSIVELY FOR
 RESIDENTS OF THE BUILDING. IF THE POOL IS DESIGNED TO
 BE ACCESSIBLE IN ACCORDANCE WITH SEC. 242.2 FBC ACC
 THEN ACCESSIBLE MEANS OF ENTRY INTO THE POOL ARE
 REQUIRED. SEC. 242.2 FBC ACC STATES:
 AT LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE
 PROVIDED FOR SWIMMING POOLS. ACCESSIBLE MEANS OF ENTRY
 SHALL BE SWIMMING POOL LIFTS COMPLYING WITH 1009.2;
 SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER WALLS
 COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING WITH
 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT LEAST
 ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL COMPLY
 WITH 1009.2 OR 1009.3.
 EXCEPTION:
 1.WHERE A SWIMMING POOL HAS LESS THAN 300 LINEAR FEET
 (91 M) OF SWIMMING POOL WALL, NO MORE THAN ONE
 ACCESSIBLE MEANS OF ENTRY SHALL BE REQUIRED PROVIDED
 THAT THE ACCESSIBLE MEANS OF ENTRY IS A SWIMMING POOL
 LIFT COMPLYING WITH 1009.2 OR SLOPED ENTRY COMPLYING
 WITH 1009.3.
 IMPORTANT NOTE: IF THE BUILDING WAS DESIGNED IN
 COMPLIANCE WITH THE FAIR HOUSING DESIGN ACT MANUAL OR
 THE FAIR HOUSING GUIDELINES CONTAINED IN THE FBC ACC
 THEN THE LIFT IS NOT REQUIRED. PLEASE REFER TO PAGE 2.7
 OF CHAPTER 2 OF THE FAIR HOUSING DESIGN ACT MANUAL, AND
 REQUIREMENT 2 IN THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES. THE MANUAL AND THE GUIDELINES REQUIRE ONLY
 AN ACCESSIBLE ROUTE TO THE COMMON USE SWIMMING POOL
 AREA BUT NOT ENTRANCE INTO THE POOL.
  
 2) SHEET P1.0: BASED ON SECS. 454.1.6.1 FBC B & TABLE
 403.6 P IT APPEARS THAT A URINAL IS MISSING IN THE
 MEN'S RESTROOM. IMPORTANT NOTE: PLEASE REVIEW THE
 EXCEPTION UNDER SEC. 403.6- WHERE A SWIMMING POOL
 SERVES ONLY A DESIGNATED GROUP OF RESIDENTIAL DWELLING
 UNITS INCLUDING HOTEL ROOMS AND NOT THE GENERAL PUBLIC,
 POOLSIDE SANITARY FACILITIES ARE NOT REQUIRED IF ALL
 LIVING UNITS ARE WITHIN A 200-FOOT HORIZONTAL RADIUS OF
 THE NEAREST WATER'S EDGE, ARE NOT OVER THREE STORIES IN
 HEIGHT UNLESS SERVICED BY AN ELEVATOR, AND ARE EACH
 EQUIPPED WITH PRIVATE SANITARY FACILITIES. PLEASE
 CLARIFY IF THIS EXCEPTION IS BEING CLAIMED.
  
 3) SHEETS P1.1. & P2.3: WASTEWATER FROM THE POOL AND
 THE COLLECTOR TANK SHALL BE DECHLORINATED AND
 DISCHARGED THROUGH AN AIR GAP IN THE INTO THE STORM
 DRAINAGE SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB
 CODE OF ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE
 INTO THE SANITARY SYSTEM AS INDICATED IN NOTE #10.
 PLEASE REVIEW WPB BUILDING DEPT. GUIDELINES FOR POOL
 WATER DISPOSAL. THE ENGINEER OF RECORD SHALL SHOW THE
 DECHLORINATION SYSTEM ON THE PLAN AND PROVIDE
 SPECIFICATIONS FOR ALL EQUIPMENT. PLEASE SEE GUIDELINES
 BELOW-
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 4) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE WATER SUPPLY LINE, SUPPLY LINE BACKFLOW PREVENTER,
 AND THE GAS WATER HEATER- SEC. 105.1 & 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  