2022-01-19 14:30:51 | FBC-2020 PLUMBING AUDIT |
| PERMIT- 21100388 |
| 1/19/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| AUDIT RESULTS: |
| |
| 1) SHEET P1.0 P1.1: THE PLANS DO NOT CLARIFY IF THE |
| RECREATIONAL FACILITIES AND SWIMMIMG POOL AT 445 DATURA |
| ARE FOR USE BY THE GENERAL PUBLIC OR EXCLUSIVELY FOR |
| RESIDENTS OF THE BUILDING. IF THE POOL IS DESIGNED TO |
| BE ACCESSIBLE IN ACCORDANCE WITH SEC. 242.2 FBC ACC |
| THEN ACCESSIBLE MEANS OF ENTRY INTO THE POOL ARE |
| REQUIRED. SEC. 242.2 FBC ACC STATES: |
| AT LEAST TWO ACCESSIBLE MEANS OF ENTRY SHALL BE |
| PROVIDED FOR SWIMMING POOLS. ACCESSIBLE MEANS OF ENTRY |
| SHALL BE SWIMMING POOL LIFTS COMPLYING WITH 1009.2; |
| SLOPED ENTRIES COMPLYING WITH 1009.3; TRANSFER WALLS |
| COMPLYING WITH 1009.4; TRANSFER SYSTEMS COMPLYING WITH |
| 1009.5; AND POOL STAIRS COMPLYING WITH 1009.6. AT LEAST |
| ONE ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL COMPLY |
| WITH 1009.2 OR 1009.3. |
| EXCEPTION: |
| 1.WHERE A SWIMMING POOL HAS LESS THAN 300 LINEAR FEET |
| (91 M) OF SWIMMING POOL WALL, NO MORE THAN ONE |
| ACCESSIBLE MEANS OF ENTRY SHALL BE REQUIRED PROVIDED |
| THAT THE ACCESSIBLE MEANS OF ENTRY IS A SWIMMING POOL |
| LIFT COMPLYING WITH 1009.2 OR SLOPED ENTRY COMPLYING |
| WITH 1009.3. |
| IMPORTANT NOTE: IF THE BUILDING WAS DESIGNED IN |
| COMPLIANCE WITH THE FAIR HOUSING DESIGN ACT MANUAL OR |
| THE FAIR HOUSING GUIDELINES CONTAINED IN THE FBC ACC |
| THEN THE LIFT IS NOT REQUIRED. PLEASE REFER TO PAGE 2.7 |
| OF CHAPTER 2 OF THE FAIR HOUSING DESIGN ACT MANUAL, AND |
| REQUIREMENT 2 IN THE FAIR HOUSING ACCESSIBILITY |
| GUIDELINES. THE MANUAL AND THE GUIDELINES REQUIRE ONLY |
| AN ACCESSIBLE ROUTE TO THE COMMON USE SWIMMING POOL |
| AREA BUT NOT ENTRANCE INTO THE POOL. |
| |
| 2) SHEET P1.0: BASED ON SECS. 454.1.6.1 FBC B & TABLE |
| 403.6 P IT APPEARS THAT A URINAL IS MISSING IN THE |
| MEN'S RESTROOM. IMPORTANT NOTE: PLEASE REVIEW THE |
| EXCEPTION UNDER SEC. 403.6- WHERE A SWIMMING POOL |
| SERVES ONLY A DESIGNATED GROUP OF RESIDENTIAL DWELLING |
| UNITS INCLUDING HOTEL ROOMS AND NOT THE GENERAL PUBLIC, |
| POOLSIDE SANITARY FACILITIES ARE NOT REQUIRED IF ALL |
| LIVING UNITS ARE WITHIN A 200-FOOT HORIZONTAL RADIUS OF |
| THE NEAREST WATER'S EDGE, ARE NOT OVER THREE STORIES IN |
| HEIGHT UNLESS SERVICED BY AN ELEVATOR, AND ARE EACH |
| EQUIPPED WITH PRIVATE SANITARY FACILITIES. PLEASE |
| CLARIFY IF THIS EXCEPTION IS BEING CLAIMED. |
| |
| 3) SHEETS P1.1. & P2.3: WASTEWATER FROM THE POOL AND |
| THE COLLECTOR TANK SHALL BE DECHLORINATED AND |
| DISCHARGED THROUGH AN AIR GAP IN THE INTO THE STORM |
| DRAINAGE SYSTEM- SEC. 454.1.6.5.15 & SEC. 90-126(5) WPB |
| CODE OF ORDINANCES. THE WASTEWATER SHALL NOT DISCHARGE |
| INTO THE SANITARY SYSTEM AS INDICATED IN NOTE #10. |
| PLEASE REVIEW WPB BUILDING DEPT. GUIDELINES FOR POOL |
| WATER DISPOSAL. THE ENGINEER OF RECORD SHALL SHOW THE |
| DECHLORINATION SYSTEM ON THE PLAN AND PROVIDE |
| SPECIFICATIONS FOR ALL EQUIPMENT. PLEASE SEE GUIDELINES |
| BELOW- |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL |
| OWNER'S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| E) FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, |
| PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 4) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| THE WATER SUPPLY LINE, SUPPLY LINE BACKFLOW PREVENTER, |
| AND THE GAS WATER HEATER- SEC. 105.1 & 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |