Date |
Text |
2021-12-03 07:41:51 | PLANS FOR THIS PROJECT ARE WITH PERMIT 21081320 |
| |
| PLEASE RESPOND TO 2ND CYCLE REVIEW COMMENTS BELOW. |
| |
| 2ND REVIEW FBC-2020 MECHANICAL |
| PERMIT-21081320 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS |
| MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE |
| PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE |
| AND A CABANA-ACCESSORY STRUCTURE. |
| |
| 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A |
| CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE |
| PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A |
| RESCHECK FOR EACH STRUCTURE SEPARATELY. |
| |
| 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY |
| SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION |
| OUTSIDE OF THE STRUCTURE. FBC RES M1411.3 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |