2021-11-05 10:36:21 | ** FAILED ** |
| |
| PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE |
| COMMENTS IN WRITING AND/OR ON THE PLANS WHERE |
| APPLICABLE: |
| |
| 1.) APPROVAL OF MASTER PERMIT #21081320 REQUIRED PRIOR |
| TO THE APPROVAL OF THIS PERMIT. |
| |
| 2.) THE TOTAL FLOOR AREA OF ALL ROOFED ACCESSORY |
| BUILDINGS ON A PROPERTY SHALL NOT EXCEED 75 PERCENT OF |
| THE GROSS FLOOR AREA OF THE PRIMARY STRUCTURE WITH A |
| MAXIMUM FLOOR AREA OF 1,000 SQUARE FEET. THE PROPOSED |
| ACCESSORY STRUCTURE EXCEEDS THIS MAXIMUM ALLOWABLE |
| BUILDING SQUARE FOOTAGE. [ZLDR S.94-304(B)(1)] |
| |
| 3.) SHOW DIMENSION ILLUSTRATING THE DISTANCE SEPARATION |
| BETWEEN THE ACCESSORY STRUCTURE AND THE PRIMARY |
| RESIDENCE TO DEMONSTRATE THAT IT MEETS THE MINIMUM 6 |
| FT. DISTANCE SEPARATION REQUIREMENT BETWEEN STRUCTURES. |
| [ZLDR S.94-304(B.)(3)] |
| |
| 4.) OVERALL HEIGHT OF THE BUILDING (FROM GRADE TO THE |
| TALLEST POINT OF THE STRUCTURE) CANNOT EXCEED 27.5 FT. |
| TOTAL. THE STRUCTURAL ELEMENTS THAT ARE PERMITTED THE |
| 10% HEIGHT EXCEPTION ABOVE THE MAXIMUM ALLOWABLE |
| BUILDING HEIGHT OF 25 FT. EXCEEDS THE LIMITATION. [ZLD |
| S.94-305(B.)(4) AND S.94-306] |
| |
| 5.) MECHANICAL EQUIPMENT MAY NOT ENCROACH MORE THAN 4 |
| FT. INTO A REQUIRED SETBACK. THERE IS AN A/C COMPRESSOR |
| UNIT ON THE SOUTH SIDE OF THE PROPOSED STRUCTURE |
| ILLUSTRATED IN THE FLOOR PLAN BUT NOT IN THE SITE PLAN. |
| PLANS MUST MATCH FOR CONSISTENCY. ALSO, THE DIMENSION |
| OF THE COMPRESSOR PAD TO THE PROPERTY LINE MUST BE |
| PROVIDED TO DEMONSTRATE CONSISTENCY WITH THE |
| REQUIREMENTS OF THE ZLDRS. [ZLDR S.94-305(B.)(4)] |
| |
| |
| NOTES: |
| |
| * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. |
| |
| * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE |
| QUESTIONS. |
| |
| * ZONE: SF14 |
| |
| * MASTER PERMIT #21081320 (NEW SFR) |
| |