Permit Number |
21100214 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-25 17:07:52 | 2ND REVIEW FBC-2020 MECHANICAL | | PERMIT-21100214 | | RESULTS FOR BOTH MAIN HOUSE AND CABANA | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS | | MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE | | PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE | | AND A CABANA-ACCESSORY STRUCTURE. | | | | 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A | | CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE | | PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A | | RESCHECK FOR EACH STRUCTURE SEPARATELY. | | | | 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY | | SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION | | OUTSIDE OF THE STRUCTURE. FBC RES M1411.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|