Plan Review Notes
Plan Review Notes For Permit 21100199
Permit Number 21100199
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2021-12-20 15:49:172ND SIGNATURE REVIEW
 12/20/21
  
 PLAN REVIEW RESULTS- DENIED.
 1) THE PREVIOUS IST REVIEW COMMENT WAS NOT ADDRESSED,
 POOL DRAWINGS 1-6- THE ENGINEER'S DIGITAL SIGNATURE IS
 SELF-CERTIFIED. THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS REQUIRES ENGINEERS TO USE A THIRD PARTY
 AGENCY TO CERTIFY THEIR DIGITAL SIGNATURES. FS 471 &
 61G15 IF YOU HAVE QUESTIONS CONTACT THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS.
  
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 2) SHEET A-1 IS NOT DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER OF RECORD- FL. STATUTE 471.025, AND SECTION
 61G15-23.005 FAC.
  