2022-03-18 12:25:51ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 03.18.2022
 PERMIT NO.: 21100054
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ PARTIALLY SATISFIED ] - PLEASE CLARIFY THE
 AUTOTURN THAT IS SHOWN ON THE ELECTRICAL SITE PLAN ? IT
 IS SHOWING THE VEHICLE TURNING THROUGH THE PROPOSED
 GUARD HOUSE. THE AUTOTURN SHOULD CORRECTLY SHOW THE
 ABILITY FOR VEHICLES TO TURN AROUND BEFORE THE GATE IF
 ENTRY INTO THE DEVELOPMENT IS DENIED.
  
 1.1 [ NEW COMMENT ] - THE NEW AUTOTURN ANALYSIS SHOWS
 VEHICLES HAVING TO MAKE A 3-POINT TURN TO TURN AROUND,
 AS WELL AS DRIVING OVER THE GRASS AREA.
  
 2. [ SATISFIED ] - IS THE LIGHTING ALONG THE NORTH SIDE
 OF THE ROADWAY PROPOSED/NEW? LIGHTING SHOULD BE
 SHIELDED AWAY FROM ADJACENT RESIDENTIAL PROPERTIES,
 PREFERABLY NOT EXCEEDING 0.5 FOOTCANDLES WHEN MEASURED
 AT THE RESIDENTIAL PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved