2022-03-22 14:28:34 | NEW GATEHOUSE |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE PROVIDE CANOPY ATTACHMENT DETAILS FBC WPB |
| 107.2.1 |
| |
| 2) PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE |
| PROVIDED PRODUCT APPROVAL THAT MEETS OR EXCEEDS THE |
| REQUIRED WIND PRESSURES SHOWN ON DRAWING S100. |
| |
| 3) ACCESSIBLE RESTROOM - RESTROOM ENTRY DOOR CANNOT |
| SWING INTO THE FIXTURE CLEAR FLOOR SPACE - UNLESS YOU |
| SHOW THE CLEAR FLOOR SPACE PER THE EXCEPTION - FBC A |
| 603.2.3 DOOR SWING. |
| DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| CLEARANCE REQUIRED FOR ANY FIXTURE. EXCEPTIONS: 2.WHERE |
| THE TOILET ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE |
| AND A CLEAR FLOOR SPACE COMPLYING WITH 305.3 IS |
| PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE DOOR |
| SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE CLEAR |
| FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY FIXTURE. |
| |
| 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE DOOR |
| MANEUVERING CLEARANCE (18" BESIDE THE LATCH SIDE) TO |
| EXIT THE RESTROOM FBC 404.2.3 |
| |
| 5) CANOPY SHOP DRAWINGS MAY BE DEFERRED SUBMITTALS BY |
| LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION |
| DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE |
| PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |