Date |
Text |
2021-11-04 07:16:22 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21100054 |
| 11/4/2021 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHOW THE LOCATION OF THE DRINKING FOUNTAINS ON THE |
| ARCHITECTURAL FLOOR PLAN AND THE PLUMBING FLOOR PLAN. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER |
| FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3. |
| 3) SHOW ON THE PLAN ALL DIMENSIONS FOR THE RESTROOM AND |
| ALL CLEAR FLOOR SPACE FOR THE PLUMBING FIXTURES PER FBC |
| ACC SEC. 604.8.1.6 |
| 4) THE BACKFLOWS FOR THE IRRIGATION SYSTEM AND THE |
| DOMESTIC WATER SYSTEM WILL REQUIRE A SEPARATE PERMIT. |
| MANUFACTURER'S SPECIFICATIONS AND A SEPARATE PLUMBING |
| PERMIT SHALL BE SUBMITTED PRIOR TO THE INSTALLATION OF |
| THESE DEVICES. THE DEVICES MUST BE INSTALLED BY A |
| LICENSED PLUMBING CONTRACTOR.F.S.489.103. |
| 5) ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE |
| (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED |
| ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN |
| ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL |
| NOT BE APPROVED. |
| 6) WHERE IS THE LOCATION OF THE WATER SOURCE? WHEN |
| HOOKING TO THE WATER SERVICE A BACKFLOW PREVENTION |
| DEVICE WILL BE REQUIRED. 602.2 POTABLE WATER REQUIRED. |
| 608.13 BACKFLOW PROTECTION. MEANS OF PROTECTION AGAINST |
| BACKFLOW SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS |
| 608.13.1 THROUGH 608.13.10. |
| 7) THE CURRENT CODE CYCLE IS FLORIDA BUILDING CODE 2020 |
| 7TH EDITION. PLEASE REMOVE AND UPDATE THE PLANS TO |
| REFLECT THE CURRENT CODE CYCLE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 8) SEPERATE PERMIT AND PLANS ARE REQUIRED FOR |
| IRRIGATION WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 9) A SERVICE SINK IS REQUIRED, PLEASE INDICATE WHERE |
| ONE WILL BE LOCATED ON THE PLANS WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6695 |
| |