2021-11-04 07:16:221ST REVIEW FBC-2020 PLUMBING
 PERMIT-21100054
 11/4/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW THE LOCATION OF THE DRINKING FOUNTAINS ON THE
 ARCHITECTURAL FLOOR PLAN AND THE PLUMBING FLOOR PLAN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 2) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3.
 3) SHOW ON THE PLAN ALL DIMENSIONS FOR THE RESTROOM AND
 ALL CLEAR FLOOR SPACE FOR THE PLUMBING FIXTURES PER FBC
 ACC SEC. 604.8.1.6
 4) THE BACKFLOWS FOR THE IRRIGATION SYSTEM AND THE
 DOMESTIC WATER SYSTEM WILL REQUIRE A SEPARATE PERMIT.
 MANUFACTURER'S SPECIFICATIONS AND A SEPARATE PLUMBING
 PERMIT SHALL BE SUBMITTED PRIOR TO THE INSTALLATION OF
 THESE DEVICES. THE DEVICES MUST BE INSTALLED BY A
 LICENSED PLUMBING CONTRACTOR.F.S.489.103.
 5) ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE
 (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED
 ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED.
 6) WHERE IS THE LOCATION OF THE WATER SOURCE? WHEN
 HOOKING TO THE WATER SERVICE A BACKFLOW PREVENTION
 DEVICE WILL BE REQUIRED. 602.2 POTABLE WATER REQUIRED.
 608.13 BACKFLOW PROTECTION. MEANS OF PROTECTION AGAINST
 BACKFLOW SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS
 608.13.1 THROUGH 608.13.10.
 7) THE CURRENT CODE CYCLE IS FLORIDA BUILDING CODE 2020
 7TH EDITION. PLEASE REMOVE AND UPDATE THE PLANS TO
 REFLECT THE CURRENT CODE CYCLE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 8) SEPERATE PERMIT AND PLANS ARE REQUIRED FOR
 IRRIGATION WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 9) A SERVICE SINK IS REQUIRED, PLEASE INDICATE WHERE
 ONE WILL BE LOCATED ON THE PLANS WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  