2021-10-08 13:28:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A 12' WIDE EXIT ROADWAY AT
 THE GATE HOUSE.
  
 THIS 12' WIDTH IS TOO NARROW/SMALL FOR A FIRE APPARATUS
 TO USE AND COULD CAUSE DAMAGE TO THE APPARATUS AND/OR
 PROPERTY.
  
 THE MINIMUM WIDTH FOR A FIRE LANE IS 20'
  
 PLEASE REVIEW AND CORRECT OR PROVIDE FOR ALTERNATIVES
 FOR EXITING FD APPARATUS.
  
  
 2) PROVIDE FOR THE LOCATION OF A FIRE EXTINGUISHERS AT
 THE GATE HOUSE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  