1 |
|
Notes |
Date |
Text |
2021-10-08 13:28:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF A 12' WIDE EXIT ROADWAY AT | | THE GATE HOUSE. | | | | THIS 12' WIDTH IS TOO NARROW/SMALL FOR A FIRE APPARATUS | | TO USE AND COULD CAUSE DAMAGE TO THE APPARATUS AND/OR | | PROPERTY. | | | | THE MINIMUM WIDTH FOR A FIRE LANE IS 20' | | | | PLEASE REVIEW AND CORRECT OR PROVIDE FOR ALTERNATIVES | | FOR EXITING FD APPARATUS. | | | | | | 2) PROVIDE FOR THE LOCATION OF A FIRE EXTINGUISHERS AT | | THE GATE HOUSE. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|