Plan Review Notes For Permit 21100036 |
Permit Number |
21100036 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2021-12-03 07:53:11 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FROM PREVIOUS LIST: | | | | 1. THE DESIGN PRESSURE REQUIREMENTS FOR A 9'X7' GARAGE | | DOORS PER BCAIB IS +38.7/-48.3, EXPOSURE C. THE DOOR | | PROPOSED HAS A LIMITATION OF +38/-44. EITHER PROPOSE A | | DIFFERENT DOOR OR PROVIDE CALCULATIONS TO SHOW HOW YOU | | HAVE DETERMINED THAT THE DOOR MEETS THE DESIGN PRESSURE | | REQUIREMENTS FOR THIS STRUCTURE, FBC R 301. | | | | HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/BCAB_PROP | | RIETARY_WIND_LOAD_CHART_FOR_ALTERATIONS_LEVEL_I.PDF | | | | ADDITIONAL PRODUCT APPROVALS WAS UPLOADED THAT DO NOT | | MEET DESIGN PRESSURE REQUIREMENTS. THE PRODUCT APPROVAL | | UPLOADED ON 11/3 HAS A DESIGN PRESSURE LIMITATION OF | | +38 / -44 PSF. THAT DOES NOT MEET THE POSITIVE OR | | NEGATIVE DP REQUIREMENTS. | | | | NOTE THAT THERE ARE NOW 3 DIFFERENT PRODUCT APPROVALS | | UPLOADED. COORDINATE WITH [email protected] TO | | HAVE ALL DOCUMENTS REMOVED EXCEPT FOR: | | | | APPLICATION | | NOC | | PRODUCT APPROVAL | | PLAN SHOWING LOCATION OF PROPOSED DOORS | | | | | | |
|