2021-12-03 07:53:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. THE DESIGN PRESSURE REQUIREMENTS FOR A 9'X7' GARAGE
 DOORS PER BCAIB IS +38.7/-48.3, EXPOSURE C. THE DOOR
 PROPOSED HAS A LIMITATION OF +38/-44. EITHER PROPOSE A
 DIFFERENT DOOR OR PROVIDE CALCULATIONS TO SHOW HOW YOU
 HAVE DETERMINED THAT THE DOOR MEETS THE DESIGN PRESSURE
 REQUIREMENTS FOR THIS STRUCTURE, FBC R 301.
  
 HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/BCAB_PROP
 RIETARY_WIND_LOAD_CHART_FOR_ALTERATIONS_LEVEL_I.PDF
  
 ADDITIONAL PRODUCT APPROVALS WAS UPLOADED THAT DO NOT
 MEET DESIGN PRESSURE REQUIREMENTS. THE PRODUCT APPROVAL
 UPLOADED ON 11/3 HAS A DESIGN PRESSURE LIMITATION OF
 +38 / -44 PSF. THAT DOES NOT MEET THE POSITIVE OR
 NEGATIVE DP REQUIREMENTS.
  
 NOTE THAT THERE ARE NOW 3 DIFFERENT PRODUCT APPROVALS
 UPLOADED. COORDINATE WITH [email protected] TO
 HAVE ALL DOCUMENTS REMOVED EXCEPT FOR:
  
 APPLICATION
 NOC
 PRODUCT APPROVAL
 PLAN SHOWING LOCATION OF PROPOSED DOORS
  
  
  