Plan Review Notes
Plan Review Notes For Permit 21100036
Permit Number 21100036
Review Stop B
Sequence Number 2
Notes
Date Text
2021-11-08 11:09:57BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: THE STRUCTURE ON THIS PARCEL THAT HAS 2 OHD'S
 IS LOCATED AT 2709 SPRUCE AVE.
  
 NOTICE: COMMENTS FROM 1ST REVIEW HAVE NOT BEEN
 ADDRESSED. SEE BELOW.
  
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE DESIGN PRESSURE REQUIREMENTS FOR A 9'X7' GARAGE
 DOORS PER BCAIB IS +38.7/-48.3, EXPOSURE C. THE DOOR
 PROPOSED HAS A LIMITATION OF +38/-44. EITHER PROPOSE A
 DIFFERENT DOOR OR PROVIDE CALCULATIONS TO SHOW HOW YOU
 HAVE DETERMINED THAT THE DOOR MEETS THE DESIGN PRESSURE
 REQUIREMENTS FOR THIS STRUCTURE, FBC R 301.
  
 HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/BCAB_PROP
 RIETARY_WIND_LOAD_CHART_FOR_ALTERATIONS_LEVEL_I.PDF
  