2021-10-24 10:43:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE DESIGN PRESSURE REQUIREMENTS FOR A 9'X7' GARAGE
 DOORS PER BCAIB IS +38.7/-48.3, EXPOSURE C. THE DOOR
 PROPOSED HAS A LIMITATION OF +38/-44. EITHER PROPOSE A
 DIFFERENT DOOR OR PROVIDE CALCULATIONS TO SHOW HOW YOU
 HAVE DETERMINED THAT THE DOOR MEETS THE DESIGN PRESSURE
 REQUIREMENTS FOR THIS STRUCTURE, FBC R 301.
  
 HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/BCAB_PROP
 RIETARY_WIND_LOAD_CHART_FOR_ALTERATIONS_LEVEL_I.PDF
  
  