Notes |
Date |
Text |
2021-10-24 10:43:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. THE DESIGN PRESSURE REQUIREMENTS FOR A 9'X7' GARAGE | | DOORS PER BCAIB IS +38.7/-48.3, EXPOSURE C. THE DOOR | | PROPOSED HAS A LIMITATION OF +38/-44. EITHER PROPOSE A | | DIFFERENT DOOR OR PROVIDE CALCULATIONS TO SHOW HOW YOU | | HAVE DETERMINED THAT THE DOOR MEETS THE DESIGN PRESSURE | | REQUIREMENTS FOR THIS STRUCTURE, FBC R 301. | | | | HTTPS://DISCOVER.PBCGOV.ORG/PZB/BUILDING/BCAB/BCAB_PROP | | RIETARY_WIND_LOAD_CHART_FOR_ALTERATIONS_LEVEL_I.PDF | | | | |
|