Plan Review Notes For Permit 21100030 |
Permit Number |
21100030 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-06 15:30:36 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) CIRCLE OR HI-LITE THE MECHANICALLY ATTACHED BASE | | SHEET FASTENING AND MAXIMUM DESIGN PRESSURE FROM THE | | ONES LISTED IN SECTION 5.8.3.2 OF THE TILE UNDERLAYMENT | | PRODUCT APPROVAL. THE REQUIRED PRESSURE IS -69.7 PSF. | | SELECT ANY OF THE ONES THAT HAVE A MAXIMUM DESIGN | | PRESSURE THAT IS MORE THAN THAT. FBC AMENDMENTS 107.2.1 |
|