Plan Review Notes
Plan Review Notes For Permit 21100008
Permit Number 21100008
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-10-06 10:28:3010/19/21
  
  
  
 *******SPOKE WITH APPLICANT. BOB MCCLURE, HE STATED THE
 PROPOSED TILE TO BE INSTALLED IS CERAMIC.*********
  
 PASSED BY FIRE.PML
  
  
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL
 PROPOSED FLOORING TILE.
  
 TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT
 CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC AND IS MANUFACTURED AROUND THE WORLD
 AND NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 TILE TYPE AND/OR PRODUCT SPEC SHEETS OF THE PROPOSED
 FINISHED FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]