Plan Review Notes
Plan Review Notes For Permit 21091369
Permit Number 21091369
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-12-13 06:56:47PASSED CRW
2021-10-05 13:25:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS LIMITED DETAIL OF THE VENTING SYSTEM,
 INCLUDING PRODUCT TYPE,LENGHTS, JOINT/FASTENING SYSTEM
 AND THE ENDING VENTILATION POINT ON THE EXTERIOR TO
 INCLUDE DIMENSIONS TO ALL NEARBY EQUIPMENT AND
 OPENINGS.
  
 PLEASE PROVIDE DETAILS
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  