Plan Review Notes For Permit 21091369 |
Permit Number |
21091369 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-13 06:56:47 | PASSED CRW | 2021-10-05 13:25:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS LIMITED DETAIL OF THE VENTING SYSTEM, | | INCLUDING PRODUCT TYPE,LENGHTS, JOINT/FASTENING SYSTEM | | AND THE ENDING VENTILATION POINT ON THE EXTERIOR TO | | INCLUDE DIMENSIONS TO ALL NEARBY EQUIPMENT AND | | OPENINGS. | | | | PLEASE PROVIDE DETAILS | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|