Plan Review Notes For Permit 21091332 |
Permit Number |
21091332 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-02-08 12:51:55 | 2ND REVIEW FBC-2020 RES. | | PERMIT- 21091332 | | 2/8/2022 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET L3: THE NEW PLAN SHEET SUBMITTED FOR THIS | | CYCLE INDICATES A 108,000 BTU GAS GRILL. PLEASE CORRECT | | THE RISER DRAWING NOTES INDICATING 16K (16,000 BTU?S) | | AND A TOTAL LOAD OF 1.444,000. BASED ON THE SPECS THE | | TOTAL LOAD OF THE SYSTEM WILL NOW BE 1,536,000 BTU?S. | | | | 2) GAS RISER: PLEASE SHOW A SHUTOFF VALVE, REGULATOR AT | | THE NEW SUPPLY LINE TO THE GAS GRILL- SECS. G2420.1, & | | G2421.1 FBC RES. | | | | 3) THE CONTRACTOR OR QUALIFIER OF RECORD SHALL PROVIDE | | HIS/HER WET SIGNATURE ON THE PLAN- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|