Plan Review Notes
Plan Review Notes For Permit 21091332
Permit Number 21091332
Review Stop G
Sequence Number 1
Notes
Date Text
2021-10-18 08:37:511ST REVIEW FBC-2020 RES.
 PERMIT- 21091332
 10/18/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE GAS GRILL- G2408.1 &
 G2447.1 FBC RES. THE SUBMITTALS MAY BE DEFERRED AND ON
 SITE FOR INSPECTION, HOWEVER PLEASE NOTE THAT TYPICALLY
 GAS GRILLS MUST BE INSTALLED WITH CLEARANCES TO
 COMBUSTIBLES PER MANUFACTURER'S RECOMMENDATIONS, AND
 ARE ALSO NOT ALLOWED TO BE INSTALLED IN ENCLOSED OR
 PARTIALLY ENCLOSED STRUCTURES WITH OVERHEAD
 CONSTRUCTION UNLESS A HOOD AND EXHAUST VENT SYSTEM IS
 INSTALLED. PLEASE REVIEW THE INSTALL MANUAL GUIDELINES
 AND PROVIDE MORE INFORMATION- SECTION 107.2.1 WPB.
  
 2) GAS RISER: PLEASE CORRECT THE BTU LOAD OF THE
 GENERATOR PER THE SPECS SUBMITTED UNDER PERMIT
 21031115. THE SPECS INDICATE 756,000 BTUS. PROVIDE THE
 SIZE OF THE PIPE FROM THE METER TO THE 1ST TEE.
 ACCORDING TO TABLE 402.4(5) FBC FG A MINIMUM 1-INCH
 PIPE IS REQUIRED FOR THE TOTAL 1,200,000 AT 140 FT.
 DEVELOPED LENGTH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  