2021-10-18 08:37:51 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21091332 |
| 10/18/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION MANUAL FOR THE GAS GRILL- G2408.1 & |
| G2447.1 FBC RES. THE SUBMITTALS MAY BE DEFERRED AND ON |
| SITE FOR INSPECTION, HOWEVER PLEASE NOTE THAT TYPICALLY |
| GAS GRILLS MUST BE INSTALLED WITH CLEARANCES TO |
| COMBUSTIBLES PER MANUFACTURER'S RECOMMENDATIONS, AND |
| ARE ALSO NOT ALLOWED TO BE INSTALLED IN ENCLOSED OR |
| PARTIALLY ENCLOSED STRUCTURES WITH OVERHEAD |
| CONSTRUCTION UNLESS A HOOD AND EXHAUST VENT SYSTEM IS |
| INSTALLED. PLEASE REVIEW THE INSTALL MANUAL GUIDELINES |
| AND PROVIDE MORE INFORMATION- SECTION 107.2.1 WPB. |
| |
| 2) GAS RISER: PLEASE CORRECT THE BTU LOAD OF THE |
| GENERATOR PER THE SPECS SUBMITTED UNDER PERMIT |
| 21031115. THE SPECS INDICATE 756,000 BTUS. PROVIDE THE |
| SIZE OF THE PIPE FROM THE METER TO THE 1ST TEE. |
| ACCORDING TO TABLE 402.4(5) FBC FG A MINIMUM 1-INCH |
| PIPE IS REQUIRED FOR THE TOTAL 1,200,000 AT 140 FT. |
| DEVELOPED LENGTH. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |