Plan Review Notes
Plan Review Notes For Permit 21091214
Permit Number 21091214
Review Stop E
Sequence Number 1
Notes
Date Text
2022-01-21 13:39:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT A COST BRAKE DOWN FOR THE REPLACEMENT OF
 THE GENERATOR. LABOR, MATERIALS. GENERATOR TO BE
 INCLUDED, TRANSFER SWITCH REPLACEMENT?
  
 SUBMIT A RISER DIAGRAM SHOWING WIRE SIZES AND LOCATION
 OF TRANSFER EQUIPMENT. 215.5