Plan Review Notes
Plan Review Notes For Permit 21091179
Permit Number 21091179
Review Stop B
Sequence Number 2
Notes
Date Text
2022-02-10 14:22:382ND AUDIT
 COMMENTS FROM THE FIRST AUDIT HAVE NOT BEEN ADDRESSED.
  
 1) [NOT RESOLVED.] ON SHEET 3 OF 12 THE ENGINEERING
 CRITERIA SPECIFIES THAT ASCE7 - 10 IS BEING USED. THE
 2020 FBC - R REFERENCES ASCE7 -16. THE 2016 EDITION OF
 ASCE7 SHOULD BE USED FOR THE 2020 FBC.
  
 2) [NOT RESOLVED.THIS CAN NOT BE DEFFERED.] THERE WAS
 NO PRODUCT APPROVAL OR SITE SPECIFIC ENGINEERING
 SUBMITTED FOR THE 3' X 8' ENTRY DOOR, TRANSOM AND
 SIDELITES. R609.2.1 CUSTOM DOORS. CUSTOM
 (ONE-OF-A-KIND) EXTERIOR DOOR ASSEMBLIES SHALL BE
 TESTED BY AN APPROVED TESTING LABORATORY OR BE DESIGNED
 AND ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICES BY A FLORIDA REGISTERED DESIGN PROFESSIONAL.
 SIGNED AND SEALED COPIES OF THE RATIONAL ANALYSIS AND
 CALCULATIONS SHALL BE PROVIDED TO THE BUILDING OFFICIAL
 UPON PERMIT APPLICATION. WIND-BOURNE DEBRIS PROTECTION
 IS REQUIRED FOR GLAZED OPENINGS PER FBC-R301.2.1.2.
  
 3) [NOT RESOLVED. THE PLANS SPECIFY A 1" FOAM BOARD
 INSULATION ON THE FLAT PART OF THE ROOF.] THERE WERE NO
 COMPONENT AND CLADDING PRESSURES SPECIFIED FOR THE FLAT
 ROOF. THE PRODUCT APPROVAL FOR THE CERTAINTEED MODIFIED
 BITUMEN ROOF SYSTEM, FL16709-R16, HAS THE ROOF CLADDING
 DESIGN PRESSURES HI-LITED ON TABLE 2C ON PAGE 5 OF 25
 FOR EXPOSURE D, ENCLOSED, GREATER THAN 30 FT AND THE
 ULTIMATE DESIGN WIND SPEED VASD OF 180MPH. THIS PROJECT
 IS LOCATED IN THE 170 MPH VULT WIND SPEED AND THE PLANS
 CORRECTLY SPECIFY THIS. ON TABLE 6 ON PAGE 21 OF THE
 PRODUCT APPROVAL FOR SYSTEM W-4 YOU HI-LITED #1
 (AS-LISTED) IN THE 180 MPH COLUMN. YOU SHOULD BE USING
 THE 170 MPH COLUMN. PLEASE NOTE THAT THERE ARE FOUR
 ROOF ZONES AND THE FASTENING REQUIREMENTS FOR EACH ZONE
 IS SPECIFIED IN THE COLUMNS OF THE TABLE. ALSO NOTE
 THAT N/A IN THE TABLE INDICATES THAT THE SYSTEM CAN NOT
 BE USED WITHIN THE PRESSURE ZONE. THEREFORE, THIS
 SYSTEM CAN NOT BE USED.
  
 4) SUBMIT A RESPONSE LETTER STATING HOW EACH OF THE
 AUDIT COMMENTS HAS BEEN ADDRESSED.