Plan Review Notes
Plan Review Notes For Permit 21091179
Permit Number 21091179
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-16 09:35:301ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 21091179
 12/16/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 12: THE 3/8-INCH SUPPLY LINES TO THE KITCHEN
 SINK, BATHTUBS AND SHOWERS ARE UNDERSIZED PER TABLE
 604.5 FBC P- MINIMUM 1/2-INCH LINES REQUIRED.
  
 2) SHEETS 11 & 12: THE SUPPLY LINES TO THE OUTDOOR
 SHOWER AND DISHWASHERS ARE NOT SHOWN IN THE ISOMETRIC
 DRAWING- SECTION 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  