2021-12-16 09:32:551ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT 21091179
 12/16/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 11 & 12: THE GAS PIPING PLAN SHOWS AN
 INDIVIDUAL BRANCH PIPE TO THE FIREPLACE DIRECTLY
 CONNECTED TO THE MAIN 2 PSI PE PIPE, BUT THE GAS
 ISOMETRIC SHOWS THE FIREPLACE PIPE CONNECTION ON THE
 BRANCH LINE SUPPLYING THE WATER HEATER- SEC. G2413.1
 FBC RES.
  
 2) SHEET 12 GAS ISOMETRIC: PLEASE LIST THE PIPE SIZING
 TABLES FOR THE LOW PRESSURE SCHEDULE 40 METALLIC-
 G2413.4(1), AND THE LOW PRESSURE CSST- G2413.4(5) FBC
 RES.
  
 3) GAS ISOMETRIC: BASED ON TABLE G2413.4(1) THE
 3/4-INCH SCHEDULE 40 BRANCH SUPPLYING TANKLESS WH #1
 AND FIREPLACE IS UNDERSIZED- MINIMUM 1-INCH REQUIRED.
  
 3) GAS ISOMETRIC: SHOW THE TYPES AND SIZES OF GAS
 PIPING FROM THE LOW PRESSURE REGULATOR TO TANKLESS WH
 #2 AND THE DRYER- SEC. G2413.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  