Date |
Text |
2021-12-16 09:32:55 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT 21091179 |
| 12/16/21 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 11 & 12: THE GAS PIPING PLAN SHOWS AN |
| INDIVIDUAL BRANCH PIPE TO THE FIREPLACE DIRECTLY |
| CONNECTED TO THE MAIN 2 PSI PE PIPE, BUT THE GAS |
| ISOMETRIC SHOWS THE FIREPLACE PIPE CONNECTION ON THE |
| BRANCH LINE SUPPLYING THE WATER HEATER- SEC. G2413.1 |
| FBC RES. |
| |
| 2) SHEET 12 GAS ISOMETRIC: PLEASE LIST THE PIPE SIZING |
| TABLES FOR THE LOW PRESSURE SCHEDULE 40 METALLIC- |
| G2413.4(1), AND THE LOW PRESSURE CSST- G2413.4(5) FBC |
| RES. |
| |
| 3) GAS ISOMETRIC: BASED ON TABLE G2413.4(1) THE |
| 3/4-INCH SCHEDULE 40 BRANCH SUPPLYING TANKLESS WH #1 |
| AND FIREPLACE IS UNDERSIZED- MINIMUM 1-INCH REQUIRED. |
| |
| 3) GAS ISOMETRIC: SHOW THE TYPES AND SIZES OF GAS |
| PIPING FROM THE LOW PRESSURE REGULATOR TO TANKLESS WH |
| #2 AND THE DRYER- SEC. G2413.3. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |