Plan Review Notes
Plan Review Notes For Permit 21091179
Permit Number 21091179
Review Stop E
Sequence Number 1
Notes
Date Text
2021-12-15 13:09:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM SHOW PANEL A AND PANEL B BOTH ARE FED
 WITH SMALLER THAN REQUIRED CONDUCTORS UNLESS THE MAINS
 IN THE METER MAIN ARE SMALLER.
  
 LOAD CALCULATION SHOWS CONDUCTORS SHOULD BE SIZE A FULL
 CAPACITY FOR THE INTENDED LOAD. 215.5
  
 PLEASE SHOW SIZE OF MAINS IN THE METER MAIN COMBO.
 215.5