2021-12-15 12:55:301ST AUDIT
  
 1) ON SHEET 3 OF 12 THE ENGINEERING CRITERIA SPECIFIES
 THAT ASCE7 - 10 IS BEING USED. THE 2020 FBC - R
 REFERENCES ASCE7 -16. THE 2016 EDITION OF ASCE7 SHOULD
 BE USED FOR THE 2020 FBC.
  
 2) THERE WAS NO PRODUCT APPROVAL OR SITE SPECIFIC
 ENGINEERING SUBMITTED FOR THE 3' X 8' ENTRY DOOR,
 TRANSOM AND SIDELITES. R609.2.1 CUSTOM DOORS. CUSTOM
 (ONE-OF-A-KIND) EXTERIOR DOOR ASSEMBLIES SHALL BE
 TESTED BY AN APPROVED TESTING LABORATORY OR BE DESIGNED
 AND ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICES BY A FLORIDA REGISTERED DESIGN PROFESSIONAL.
 SIGNED AND SEALED COPIES OF THE RATIONAL ANALYSIS AND
 CALCULATIONS SHALL BE PROVIDED TO THE BUILDING OFFICIAL
 UPON PERMIT APPLICATION. WIND-BOURNE DEBRIS PROTECTION
 IS REQUIRED FOR GLAZED OPENINGS PER FBC-R301.2.1.2.
  
 3) THERE WERE NO COMPONENT AND CLADDING PRESSURES
 SPECIFIED FOR THE FLAT ROOF. THE PRODUCT APPROVAL FOR
 THE CERTAINTEED MODIFIED BITUMEN ROOF SYSTEM,
 FL16709-R16, HAS THE ROOF CLADDING DESIGN PRESSURES
 HI-LITED ON TABLE 2C ON PAGE 5 OF 25 FOR EXPOSURE D,
 ENCLOSED, GREATER THAN 30 FT AND THE ULTIMATE DESIGN
 WIND SPEED VASD OF 180MPH. THIS PROJECT IS LOCATED IN
 THE 170 MPH VULT WIND SPEED AND THE PLANS CORRECTLY
 SPECIFY THIS. ON TABLE 6 ON PAGE 21 OF THE PRODUCT
 APPROVAL FOR SYSTEM W-4 YOU HI-LITED #1 (AS-LISTED) IN
 THE 180 MPH COLUMN. YOU SHOULD BE USING THE 170 MPH
 COLUMN. PLEASE NOTE THAT THERE ARE FOUR ROOF ZONES AND
 THE FASTENING REQUIREMENTS FOR EACH ZONE IS SPECIFIED
 IN THE COLUMNS OF THE TABLE. ALSO NOTE THAT N/A IN THE
 TABLE INDICATES THAT THE SYSTEM CAN NOT BE USED WITHIN
 THE PRESSURE ZONE. THEREFORE, THIS SYSTEM CAN NOT BE
 USED.