2022-01-11 16:36:09 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 21091113 807 N FLAGLER DR |
| |
| 2ND REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| APPROVAL. |
| |
| 2A) SECOND REQUEST: THE WATER CLOSET SHALL BE |
| POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO |
| ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE |
| WALL OR PARTITION PER FBC ACC 604.2. |
| TO BE CLEAR, SHOW THE CENTERLINE OF THE WATER CLOSET |
| FROM THE SIDE WALL. |
| |
| 2B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| WALL PER FBC ACC 604.3.1 |
| SECOND REQUEST: PROVIDE DIMENSIONS ON THE PLAN AND SHOW |
| CLEARANCE IN GIRLS RR. |
| |
| 2C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| REAR WALL TO CENTER OF WALL ATTACHMENT (SEE FBC ACC |
| FIGURE 604.5.1) AND |
| SECOND REQUEST SHOW GRAB BAR EXTENDING 54 INCHES |
| MINIMUM FROM THE REAR WALL PER FBC ACC 604.5.1 |
| |
| 4. MINIMUM FACILITIES; PER WPB FBC 107.2.1, PROVIDE THE |
| FOLLOWING: |
| NEW COMMENT: RESPONSE NOTED ON PLUMBING COMMENTS. PER |
| WPB FBC 107.2.1, NOTE THE OCCUPANCY/OCCUPANCY LOAD AND |
| MINIMUM FACILITY PLUMBING SCHEDULE ON THE PLANS. |
| |
| 5. PER WPB FBC 107.2.1, REVISE FINISH WALL SCHEDULE FOR |
| CUSTODIAL ROOM. REFER TO FBC PL 310.3 AND FBC 1210.2.2. |
| WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT |
| THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS |
| THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE |
| THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD |
| BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND |
| SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| NEW COMMENT: DEFER TO BUILDING PLANS EXAMINER |
| |
| 7. P-6.01PER FBC PL 914.2, A CIRCUIT VENT CONNECTION |
| SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM (CIRCUIT |
| VENTED) FIXTURE DRAINS (FLOOR DRAINS IN THIS CASE) ON |
| THE BRANCH SERVICING THE BOYS AND GIRLS RESTROOMS. |
| SECOND REQUEST: PROVIDE CIRCUIT VENT CONNECTION BETWEEN |
| THE TWO UPSTREAM FLOOR DRAINS. TO BE CLEAR, THIS CANNOT |
| BE ACCOMPLISHED BY USING A DOUBLE WYE OR COMBINATION |
| WYE AND EIGHTH BEND. A WYE DOWNSTREAM FOR ONE FLOOR |
| DRAIN, THEN A COMBO ON ITS BACK FOR THE VENT THEN A |
| COMBO UPSTREAM FOR THE SECOND FLOOR DRAIN PROVIDES THE |
| NECESSARY CONFIGURATION. |
| |
| 17. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR HOT |
| WATER PIPING INSULATION COMPLYING WITH FBC EC TABLE |
| C403.2.10. |
| NEW COMMENT: PROVIDE IN SUPPORTING DOCUMENTS DEDICATED |
| "ROSARIAN ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL |
| EAST SPECIFICATION 22 07 00 PLUMBING INSULATION" |
| NEW COMMENT: PROVIDE NOTE "PROVIDE INSULATION OF |
| PLUMBING PIPING SYSTEMS IN ACCORDANCE WITH ROSARIAN |
| ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL EAST |
| SPECIFICATION 22 07 00" |
| |
| |
| 19. PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION |
| FOR PLUMBING PIPING SYSTEMS. SUPPORTING DOCUMENT SGM |
| MEP IS INCOMPLETE. |
| NEW COMMENT: PROVIDE IN SUPPORTING DOCUMENTS DEDICATED |
| "ROSARIAN ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL |
| EAST SPECIFICATION 22 11 16 DOMESTIC WATER PIPING" |
| NEW COMMENT: PROVIDE NOTE "PROVIDE PIPING SYSTEMS IN |
| ACCORDANCE WITH ROSARIAN ACADEMY RENOVATIONS TO |
| RESTROOM-LEWIS HALL EAST SPECIFICATION 22 11 16 |
| DOMESTIC WATER PIPING" |
| |
| |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |