2022-01-11 16:36:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21091113 807 N FLAGLER DR
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 2A) SECOND REQUEST: THE WATER CLOSET SHALL BE
 POSITIONED WITH A WALL OR PARTITION TO THE REAR AND TO
 ONE SIDE. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE
 WALL OR PARTITION PER FBC ACC 604.2.
 TO BE CLEAR, SHOW THE CENTERLINE OF THE WATER CLOSET
 FROM THE SIDE WALL.
  
 2B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 SECOND REQUEST: PROVIDE DIMENSIONS ON THE PLAN AND SHOW
 CLEARANCE IN GIRLS RR.
  
 2C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL TO CENTER OF WALL ATTACHMENT (SEE FBC ACC
 FIGURE 604.5.1) AND
 SECOND REQUEST SHOW GRAB BAR EXTENDING 54 INCHES
 MINIMUM FROM THE REAR WALL PER FBC ACC 604.5.1
  
 4. MINIMUM FACILITIES; PER WPB FBC 107.2.1, PROVIDE THE
 FOLLOWING:
 NEW COMMENT: RESPONSE NOTED ON PLUMBING COMMENTS. PER
 WPB FBC 107.2.1, NOTE THE OCCUPANCY/OCCUPANCY LOAD AND
 MINIMUM FACILITY PLUMBING SCHEDULE ON THE PLANS.
  
 5. PER WPB FBC 107.2.1, REVISE FINISH WALL SCHEDULE FOR
 CUSTODIAL ROOM. REFER TO FBC PL 310.3 AND FBC 1210.2.2.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT
 THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS
 THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE
 THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD
 BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
 NEW COMMENT: DEFER TO BUILDING PLANS EXAMINER
  
 7. P-6.01PER FBC PL 914.2, A CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM (CIRCUIT
 VENTED) FIXTURE DRAINS (FLOOR DRAINS IN THIS CASE) ON
 THE BRANCH SERVICING THE BOYS AND GIRLS RESTROOMS.
 SECOND REQUEST: PROVIDE CIRCUIT VENT CONNECTION BETWEEN
 THE TWO UPSTREAM FLOOR DRAINS. TO BE CLEAR, THIS CANNOT
 BE ACCOMPLISHED BY USING A DOUBLE WYE OR COMBINATION
 WYE AND EIGHTH BEND. A WYE DOWNSTREAM FOR ONE FLOOR
 DRAIN, THEN A COMBO ON ITS BACK FOR THE VENT THEN A
 COMBO UPSTREAM FOR THE SECOND FLOOR DRAIN PROVIDES THE
 NECESSARY CONFIGURATION.
  
 17. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR HOT
 WATER PIPING INSULATION COMPLYING WITH FBC EC TABLE
 C403.2.10.
 NEW COMMENT: PROVIDE IN SUPPORTING DOCUMENTS DEDICATED
 "ROSARIAN ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL
 EAST SPECIFICATION 22 07 00 PLUMBING INSULATION"
 NEW COMMENT: PROVIDE NOTE "PROVIDE INSULATION OF
 PLUMBING PIPING SYSTEMS IN ACCORDANCE WITH ROSARIAN
 ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL EAST
 SPECIFICATION 22 07 00"
  
  
 19. PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION
 FOR PLUMBING PIPING SYSTEMS. SUPPORTING DOCUMENT SGM
 MEP IS INCOMPLETE.
 NEW COMMENT: PROVIDE IN SUPPORTING DOCUMENTS DEDICATED
 "ROSARIAN ACADEMY RENOVATIONS TO RESTROOM-LEWIS HALL
 EAST SPECIFICATION 22 11 16 DOMESTIC WATER PIPING"
 NEW COMMENT: PROVIDE NOTE "PROVIDE PIPING SYSTEMS IN
 ACCORDANCE WITH ROSARIAN ACADEMY RENOVATIONS TO
 RESTROOM-LEWIS HALL EAST SPECIFICATION 22 11 16
 DOMESTIC WATER PIPING"
  
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  